Parameter
Prerequisite
Description
User interface
Energy flow
With order code for "Sensor version":
• option "Mass (integrated
temperature measurement)"
or
• option "Mass (integrated pressure/
temperature measurement)"
Displays the energy flow that is
currently calculated.
Dependency
The unit is taken from the Energy flow
unit parameter (→ See 10.4.2).
Signed floating-point
number
Heat flow difference
• In the Select gas type parameter
(→ See 10.4.3), one of the following
options is selected:
Single gas
Gas mixture
Natural gas
User-specific gas
Displays the heat flow difference that is
currently calculated.
Dependency
The unit is taken from the Energy flow
unit parameter (→ See 10.4.2).
Signed floating-point
number
Reynolds number
Displays the Reynolds number that is
currently calculated.
Signed floating-point
number
Density
Displays the density currently
measured.
Dependency
The unit is taken from the Density unit
parameter.
Positive floating-point
number
Specific volume
Displays the current value for the
specific volume.
Dependency
The unit is taken from the Specific
volume unit parameter.
Positive floating-point
number
Pressure
The Pressure option is selected in the
External value parameter.
Displays the current process pressure.
Dependency
The unit is taken from the Pressure
unit parameter.
0 to 250 bar
Compressibility factor
The Gas option or the Steam option is
selected in the Select medium
parameter.
Displays the compressibility factor
currently calculated.
0 to 2
Degrees of superheat
In the Select medium parameter, the
Steam option is selected.
Displays the degree of superheating
currently calculated.
0 to 500 K
-
-
-