7 Maintaining the product
153
Pos: 182 /TD/Überschriften/3.2 Technische Daten @ 0\mod_1176211088437_79.docx @ 704 @ 3 @ 1
7.10.
Technical data
Pos: 183 /TD/Leistungsbeschreibung/Technische Daten/testo Saveris/01 Basisstation @ 0\mod_1191323639453_79.docx @ 5302 @ 3 @ 1
7.10.1.
Saveris base
Characteristic
Values
Memory
40,000 values per channel (total max.
18,000,000 values)
Dimensions
225 x 150 x 49 mm
Weight
approx. 1510 g
Protection class
IP42
Housing material
Die-cast zinc/plastic
Radio frequency
868 MHz/2.4 GHz
Power supply
6.3 V DC mains unit; alternatively via 24
V AC/DC plug-in/screw terminals, power
consumption < 4 W.
Rech. batt.
1
Li-ion battery
The rechargeable battery is used only for
backing up data and for emergency SMS
in the event of failure of the power supply,
not for the power supply during operation.
Operating
temperature
+5 ... +45 °C
Storage
temperature
-25 ... +60 °C
Display
Graphical LCD display
Interfaces
USB, radio, Ethernet
Number of radio
probes
Max. 15 probes can be connected directly
via radio interface,
max. 150 total via radio/router/converter
and Ethernet,
max. 450 channels.
Alarm relay
max. 1 A, max. 30 W, max. 60/25 V
DC/AC, NC or NO contact
GSM module
850/900/1800/1900 MHz
1
Wearing part