6.8
Personnel sensor
The Personnel Sensor is supplied as a single transmitter / receiver unit.
6.8.1
Installing the personnel sensor
1.
Use the mounting template illustrated in Figure 56 and the fixing screws provided to mount
the Personnel Sensor. Mount the sensor centrally to the front of the fume hood and above
the fume hood sash, use the fixing holes in the back of the sensor.
See the table in Figure 56 for the correct mounting hole dimensions and locations.
A
Cable Entry
10 x 20 mm (5 mm diameter cable provided)
B
Fixing Hole
5 mm diameter maximum
C
Spare Hole
10 x 20 mm
D
Spare Hole
10 x 20 mm
E
Fixing Hole
5 mm diameter maximum
F
Spare Fixing Hole
5 mm diameter maximum
Figure 56: Personnel sensor mounting details
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...