AFA4000/E
VAV Airflow Controller / p.161
Menu item
Option
Instructions
Sensors (cont.)
Personnel (Sensor)
Set the input activation for the personnel
sensor:
•
Normally Open (N/O) Contact
•
Normally Closed (N/C) Contact
Disabled
Sash String Type
Set the input activation for the sash
string:
•
SP1-50
•
SP-120
Motor Drive
Motor Voltage
Set the motor voltage:
6-24V
Motor Speed Open
Set the motor speed:
30-100%
Motor Speed Closed
Set the motor speed:
30-100%
Clutch Off Delay
Set the delay time:
0.0-1.00sec
Overcurrent Open
Set the overccurent level:
50-3000mA
Overcurrent Close
Set the overccurent level:
50-3000mA
Stall Detect Sensitivity
Set the sensitivity level:
1-6
Stall Detect Delay
Set the delay time:
1-5 Seconds
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...