Menu item
Option
Instructions
Auto Open Delay
Set the delay time:
0-10 Seconds
Auto Open (cont.)
Auto Open Alarm
Set the delay time:
0-10 Seconds
Auto Lock
Enable / Disable
Set the required action:
•
Enable
•
Disable
Auto Lock Alarm
Set the alarm delay time:
0-10 Seconds
Auto Lock Calibration
Calibrate the Lock position
Auto Stop
Enable / Disable
Set the required action:
•
Enable
•
Disable
Auto Stop Distance
Set the lock distance:
5-99mm
Auto Stop Delay
Set the delay time:
1-5 Seconds
8.6.2.3
BMS input settings
Menu item
Option
Instructions
BMS Input Settings
Fire Alarm
Set the Fire Alarm BMS input:
•
Disabled
•
Input 1
–
4 open
•
Input 1
–
4 closed
Open Sash
Set the Open Sash BMS input:
•
Disabled
•
Input 1
–
4 open
•
Input 1
–
4 closed
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...