AFA4000/E
VAV Airflow Controller / p.145
8.5
Dual Output
–
Econ Output 2
The AFA4000/E has a second 0
–
10V control output that is available when the Econ power
supply unit is fitted. It can be configured for 4 functions using the pushbutton menu.
Function
Additional requirements
Description
Bleed damper
•
Econ power supply unit
0
–
10 Vdc output to control a
secondary damper e.g. fresh air bleed
or supply air damper
Volume pressure
•
Econ power supply unit
•
Pressure cell PCB
•
Duct restrictor device
0
–
10 Vdc volumetric output based on
duct volume measurement
Volume
•
Econ power supply unit
•
Sash position sensor
0
–
10 Vdc volumetric output based on
sash position and face velocity
calculation
Face Velocity
•
Econ power supply unit
0
–
10 Vdc face velocity retransmission
output, 0-10Vdc / 0-1.00m/sec
(200fpm) e.g. 0.50m/sec = 5Vdc
8.5.1
Bleed Damper
The bleed damper function is used to operate a secondary output based on the Econ Output 1
voltage. It can be scaled and offset to give the required output direction and range. Examples
are using the second output as a Fresh Air or Room Air Bleed control voltage signal.
To access the ECON Configure Menu, navigate to
Main Menu
>
Set up Monitor
>
Configure
>
Econ Config
.
Press the
↓
button to scroll down the menu list and press
Mute
to select the required option.
Note: The Configure menu is password protected. The default password is 0 0 0 0.
Note: The Monitor Set up Menu also includes Calibration and Password sub-menus which are
used by engineers to set up the system. If you enter any of the Monitor Set up sub-menus
by accident, press the
↑
and
↓
arrows together when the password is requested to
return to the Monitor Set up menu.
1.
Select
Output Type
from the Econ Configure menu and press
Mute
to continue.
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...