AFA4000/E
VAV Airflow Controller / p.169
Figure 74: Typical connection diagram
Press the
↑
and
↓
arrows to scroll through the menu list and press
Mute
to select the required
option.
Setting up the temperature input:
1.
From the
Requires set up
screen, press
Mute
, or from the
Run Screen
press and hold
the
Mute
button for 5 seconds until the
Main Menu
is displayed.
2.
Select
Set Up Monitor > Configure
.
3.
Enter the password (the factory default password is 0-0-0-0) and press
Mute
to continue.
4.
Select
Input 3
>
Analog
> Temperature
. The Temperature sub-menu displays:
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...