AFA4000/E
VAV Airflow Controller / p.22
3.6.6.4
Sash position sensor
Auxiliary sash position sensor used for volumetric output and sash high alarms with dedicated
input on the Econ power supply.
3.6.6.5
Mains fail battery unit
Auxiliary plug-in battery unit has a mains fail alarm. This requires inverter type control only and
is not to be used if the Econ power supply is fitted.
3.6.6.6
Auto sash keypad
RJ45 connection for the Auto Sash keypad. Refer to sections 4 and 7.6 for Auto Sash functions.
3.7
Functions
3.7.1
Airflow functions
The AFA4000/E airflow display can be set up using the pushbutton menus to display airflow in
units of m/sec or fpm and can also be set to show plain text
Air Safe
&
Air Fail
only.
The AFA4000/E has 4 programmable airflow alarms:
Alarm
Description
Safe airflow
•
Airflow reading above warning level
(for example, > 0.45 m/sec)
•
Green Safe LED Halo illuminated
•
Air Safe
displayed in the status window or main window if
Show Airflow is set to OFF.
Warning airflow
•
Airflow reads between warning level and air fail level (for
example, > 0.4 m/sec and < 0.45 m/sec)
•
Amber Warning LED Halo illuminated.
•
Air Safe
displayed in the status window or main window if
Show Airflow is set to OFF.
Low airflow
•
Airflow reads below alarm level for longer than the warning to
low air delay time
•
Red Alarm LED Halo illuminated
•
Air Fail
displayed in the status window or main window if
Show Airflow is set to OFF.
•
Audible alarm sounds - can be muted by pressing the
Mute
pushbutton
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...