AFA4000/E
VAV Airflow Controller / p.127
item
Instructions
Output Type
The 0
–
10 Vdc control output can be set to the following
options:
Damper:
The damper output is linearised for a
butterfly-type damper so that the output is
proportional to volume and not damper
position. The linearised output gives
increased speed of response when the sash
is opened.
This setting should be used for TEL supplied
Econ VAV dampers.
The damper output is direct and 10V = Max
volume.
Inverter:
The inverter output is proportional to
volume when used with an inverter and is
reversed so 0V = Max volume.
Valve:
The valve output is proportional to damper
position. For example, 50% = 45° on a 90°
actuator. The output is direct and 0V = Max
volume.
Figure 65: Typical butterfly damper curve to face velocity
(Valve Output)
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...