AFA4000/E
VAV Airflow Controller / p.156
Parameter
Description
Range
Sash Width
Enter the internal Fume Cupboard width 0-7000 mm
Sash Gap
Volumetric Output volume range for 0-10
Vdc
0-1000 mm
Max Volume
Enter the maximum fume cupboard
volume or required range
1 to 1000 l/sec
5.
Select
Sash Width
, then use the
↑
and
↓
arrows to enter the measured internal width. Press
Mute
. (Default value: 0
–
1200 mm).
6.
Select
Sash Gap
, then use the
↑
and
↓
arrows to enter the measured gap value. Press
Mute
.
(Default value: 25 mm). (for example, the gap between the sash and soffit panel (e.g. 25
mm)).
7.
Select
Max Volume
, then use the
↑
and
↓
arrows to adjust the value so the volumetric
output range is equal to the required fume cupboard volume range. Press
Mute
. (Default
value: 1000 l/sec). Select
Done
and
Run
. For example, setting the Max Volume 1000 l/sec
will give 10 Vdc @ 10,000 l/sec, setting the Max Volume to 500 l/sec will give 10 Vdc @ 500
l/sec etc.
8.5.4.1
Calibration
Once the settings described above have been entered, the sash position sensor must be
calibrated:
1.
Navigate to
Main Menu
>
Set up Monitor
>
Calibration
.
Note: The Calibration menu is password protected. The default password is 0 0 0 0.
2.
Select
Sash Position Sensor
.
3.
Follow the on-screen instructions to move the sash to the first position (normal working
height, approximately 500 mm).
4.
Use the
↑
and
↓
arrows to enter the sash height. Press
Mute
.
5.
Follow the on-screen instructions to lower the sash to the second position (approximately
half way, 250 mm).
6.
Use the
↑
and
↓
arrows to enter the sash height. Press
Mute
.
Select
Done
, followed by
Run
.
8.5.4.2
Testing
When the sash position sensor has been calibrated, and the extract fan is running, the measured
volume will display in the Diagnostics Menu I/O Status
–
Sensor Data screen (section 13.2).
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...