AFA4000/E
VAV Airflow Controller / p.131
item
Instructions
Integral Time (cont.)
The ideal setting for this value is to select a value as high as
possible that gives stable control of the damper or Inverter
without ‘hunting’. Ref
er to section 0 for a practical
explanation of how to set this value on a fume cupboard.
Boost Duration
This function is used in conjunction with the Sash position
sensor for VAV control.
When the sash is opened, the output drives to a calculated
position for a brief time period before the output switches
back to face velocity control. The Boost Duration is the time
period that the output is held before switching back to face
velocity control.
This parameter should not require an on-site setting and is
factory set to 5 seconds.
Boost Percentage
This function is used to adjust the pre-determined output
position that the damper drives to when the boost function
is active.
Done
Return to the
Monitor Config menu
(section 8.1.1).
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...