AFA4000/E
VAV Airflow Controller / p.193
Menu
Parameter/Action
I/O Status
Input Data
. This displays the following:
•
Input 1
On / Off, Analogue i/p voltage or Not Used
•
Input 2
On / Off, Analogue i/p voltage or Not Used
•
Input 3
On / Off, Analogue i/p voltage or Not Used
Note: On = input closed; Off = input open; analogue input voltage
= 0
–
5 Vdc.
Output Data
. This displays the following:
•
Output 1
On / Off
•
Output 2
On / Off
•
Output 3
On / Off
•
AOut 1
Analogue o/p 1 voltage
•
AOut 2
Analogue o/p 2 voltage
Note: On = output closed; Off = output open or not assigned;
analogue output voltage = 0
–
10 Vdc.
Sensor Data
. This displays the following:
•
Airflow
0 - 100%. Output of airflow sensor in %
where 0% is maximum airflow and 100% is
no airflow
•
Volume
Measured or calculated volume in l/sec or
CFM (when enabled)
•
Sash position
Sash opening in mm or inches (when
enabled)
•
Temperature
Temperature in °C or °F (when enabled)
Hours Counter
Displays the hours that the fan has run since the last Hours Counter
reset.
Auto Sash Data
(only
when Auto Sash is
connected)
•
Position Status. The sash position is shown as % open when sash
position sensor is used
•
Alarm On / Off status
•
Moving On / Off status
•
Sash Closed On / Off status
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...