VAV Airflow Controller / p.170
Parameter
Description
Range
A
Temperature Units
Display units
°C or °F
B
Low Temperature Alarm
Sets the Low Temperature Alarm
point
0.0 to High Alarm
value
C
High Temperature Alarm
Sets the High Temperature Alarm
point
100.0 to Low Alarm
value
D
Show Temperature
Turns the temperature display
On / Off
Yes / No
E
Offset
Allows the measured value to be
offset
-5.0 °C to +5.0 °C
Note: The temperature sensor is accurate to 0.5 °C. The offset parameter can be used, if the
displayed value needs to be changed to match a 3rd party instrument or other
equipment.
5.
Select
Temperature Units
>
Centigrade / Fahrenheit
.
6.
Select
Low Temperature Alarm
, then use the
↑
/
↓
buttons to set the alarm point.
7.
Select
High Temperature Alarm
, then use the
↑
/
↓
buttons to set alarm point.
8.
Select
Show Temperature
, then select
Enabled
or
Not Enabled
9.
Select
Offset
, and then select
Done
.
10.
In the
Monitor Config Menu
, select
Low Temperature Relay
, and use the
↑
/
↓
buttons to set
the relay output.
11.
In the
Monitor Config Menu
, select
High Temperature Relay
, and use the
↑
/
↓
buttons to
set the relay output.
12.
Select
Done > Run
.
9.2.1
Testing
Once the temperature sensor function has been configured the temperature will display in the
diagnostics menu I/O Status.
The sensor data screen is described in section 13.2.
Summary of Contents for AFA4000/E
Page 1: ...AFA4000 E VAV Airflow Controller Installation and operating manual Issue 2...
Page 57: ...AFA4000 E VAV Airflow Controller p 57 Figure 22 AFA4000 E inverter control connections...
Page 58: ...AFA4000 E VAV Airflow Controller p 58 Figure 23 AFA4000 E damper control connections...
Page 59: ...AFA4000 E VAV Airflow Controller p 59 Figure 24 AFA4000 E typical connection diagram...
Page 60: ...AFA4000 E VAV Airflow Controller p 60 Figure 25 AFA4000 E AS typical connection diagram...
Page 62: ...AFA4000 E VAV Airflow Controller p 62 Figure 27 SM7 airflow sensor dimensions...
Page 96: ...AFA4000 E VAV Airflow Controller p 96 6 9 Auto Sash System Control Box general wiring diagram...
Page 158: ...AFA4000 E VAV Airflow Controller p 158...
Page 182: ...AFA4000 E VAV Airflow Controller p 182 Figure 79 Connection diagram with RS232 485 converter...