ACCESS CODE
Access Code
number
21
0 - 250
Press ENTER to edit the Access Code at this
location. If correct this will then allow access to the
“Sub Menus”. Once the Access Code is input it will
remain active for 25 minutes after the last key
press. Standard security will then resume and
access into the submenus will require re-entering of the Access Code.
The system will then automatically lock the use of
the keys which control the ON/OFF and
AUTOMATIC and MANUAL Functions. This is
designed to protect the system from tampering.
If a message KEPAD LOCKED appears on the screen enter the ACCESS CODE to allow
access.
SETTINGS
SETTINGS
*LoLevel Shutdown
*150
0 - 9999
*LoLevel Alarm
*150
0 - 9999
*Low Limit
*OFF
*OFF
*Cut In Level (1,2,3)
200
0 - 9999
*Cut Out Level (1/2/3)
450
0 - 9999
*HiLevel Shutdown
650
0 - 9999
*HiLevel Alarm
650
0 - 9999
*High Limt
*OFF
*OFF
Alt Cut In 2
250
0 - 9999
Alt Cut Out 2
500
0 - 9999
Alt Cut In 3
300
0 - 9999
Alt Cut Out 3
600
0 - 9999
*Trip Point Low
300
0 - 9999
*Trip Point High
400
0 - 9999
Low Level Shutdown
Low Level Alarm
Low Limit
This is the alarm level point for low liquid level. If
any pump is running and the system falls below this level and remains there for the
period of the “LoLevel Delay” time the system will act according to the setting in the “Low
Limit Action” Sub menu.
➢
If Low Limit Action is set to OFF, then no action is taken.
➢
If Low Limit Action is set to Alarm, then an alarm is only logged.
➢
If Low Limit Action is set to Shutdown, then a shutdown is initiated.
For alarm and shutdown actions, an output relay can be set to the appropriate mode to
turn it on.
LoLevel Shutdown
XXXX
Access Code
XXX
*KEY PAD LOCKED*
Enter Access Code