OUTPUTS
OUTPUTS
Digital Output 1
selection Shutdown Fault
Shutdown Fault,
Lo Level Fault,
Hi Level Fault,
*Pump 1 - 6 Run,
Digital Output 2
selection Any Pump Shutdown
*Pump 1 - 6 Fault,
System Paused,
Low Alarm, High Alarm,
Any Alarm,
Digital Output 3
selection Any Alarm
Any Pump Shutdwn,
Any Pump Running,
Trip Point
Alternate Trip,
*Digital Output 4
selection Any Pump Running,
Aux Output 1,
Aux Output 2,
Aux Output 3,
Shutdown Fault
Analogue Output 1
selection System Level
System Level
* If the Jockey Pump is set to "ON" then Digital Output 4 will not be avaialable for other functions.
* Pump Run 2 - 6 are only visible if "Number of pumps" is set accordingly
* Pump Fault 2 - 6 are only visible if "Number of pumps" is set accordingly
SWO has four main programmable outputs that can be used to communicate
with external sources such as Telemetry or Building Management Systems (BMS). As
each system requires different combinations of information all output relays are
configurable in software. All outputs are Voltage Free - Change Over contact outputs and
capable of 5 amps 240 VAC.
You can view which outputs are currently activated within the PUMP DATA LOG menu,
under Digital Output State. The status of the analogue outputs is also available within this
menu.