Min Pump Runtime
This setting is used to prevent switchgear and pumps
from failing due to excessive cycling. Each pump is
prevented from stopping until its own Minimum run timer expires.
A message will appear on the status screen letting you
know that it has occurred.
This method of protection should only be used if the reticulation system can withstand
maximum pump head.
Maximum Pump Starts
This setting is used to prevent switchgear and pumps
from failing due to excessive cycling. Each pump is
prevented from tarting if the Max starts per hour setting has been exceeded.
A message will appear on the status screen letting you
know that it has occurred.
Note: The “Min Pump Runtime” and “Max Pumps Starts” screens are visible according to
the setting of “Excess Run Prot’n” sub menu in the “Configuration” Menu.
Min Pump Runtime
XXX seconds
Max Pump Starts
XXX per Hr
PUMP/S REACHED
MAX Starts PerHr
Min Run Time ON
Pump Stop X Secs