www.techsys.com.au
Version 1.3 11/12/11
14
C o r p o r a t io n
Main Menu
Sub Menu
Units
Defaults
Range
CONFIGURE
Operating Mode
selection MultiLevel
Pressure, Flowrate,
Temperature, Single Level
Multi Level.
*Control Mode
Tank Empty
Tank Fill
Number of pumps
number
3
0 - 6
*Transducer Zero
unitless
0 - 9999
*Adjust Level
unitless
0 - 9999
*Averaging
number
20
0 - 50
Scale An Output
number
1000
Pump Flow Rate
per Min
5
1-9999 /Min
Auto Rotation
selection Full
Full, *Pump 1 - Pump 6,
Every 24 Hours, Low Hours.
LoLevel Restarts
selection 0
0 - 250
Sensing Input
selection Analogue
Analogue, Switched
Cycle Protection
selection Minimum Run Time
Minimum Run Time,
Max Starts PerHr
Low Limit Action
selection OFF
OFF, Alarm, Shutdown
HighLimit Action
selection OFF
OFF, Alarm, Shutdown
User Access Code
number
21
0 - 250
* "Transducer Zero", "Adjust Pressure" & "Averaging" are hidden when in "Switched" mode
* Pumps 2 - 6 are only visible if "Number of pumps" is set accordingly
* Pending Tank Fill or Tank Empty selection will reverse some logic . i.e Cut in level nowCut Out level etc
Main Menu
Sub Menu
Units
Defaults
Range
JOCKEY PUMP
Jockey Pump
selection ----Off----
----Off----, ===On===
*JP Cut In Level
250
0 - 9999
*JP Cut Out Level
400
0 - 9999
*JP Run On Time
seconds
2
0 - 999
"JP In Delay Time
seconds
0
0 - 999
* JP Screens are only visible is "Jockey Pump" is set to " ===ON==="