SYSTEM STATUS
System Level
number
display
0 - 9999
Flow Rate /Min
number
display
0 - 9999
System Level
The System Level is the direct measurement of the
level in the tank / sump of the system. It is read from
the level transducer and is displayed
on the Level Screen on the front of the switchboard.
This is the default display screen. It will display appropriate messages describing current
conditions. These include in order of priority: Emergency Stop, Hi Level Alarm, Lo Level
Shutdown, Fault, Pause Activated, etc.
After 25 minutes from the last key press the SWO will revert to this screen
automatically.
Flow Rate
The SWO can operate on a calculated flow
rate.
The Calculated flow rate uses information that is input into the Pump Flow rate screen to
provide an estimation of the flow rate at any time. This calculation automatically
compensates for the number of pumps operating - it is useful in determining the system
capacity. This is a calculated flow and must be treated as such. The time base for this
flow is in flow per
MINUTES
and is not adjustable.
FAULT HISTORY
FAULTS
Fault 1
selection None
None Logged
Logged
Lo Press Shutdwn,
Fault 2
selection None
Hi Press Shutdwn,
Logged
No Flow Shutdwn,
Fault 3
selection None
*Pump 1 - 6 Shutdown
Logged
*Pump 1 - 6 No Flow
Fault 4
selection None
Power Off
Logged
Power Glitch
Fault 5
selection None
Auto Reboot
Logged
When a system fault
is registered a “NEW FAULT” message will appear on the main
screen. It will also be logged in the FAULT HISTORY menu. There is space for up to 5
faults to be logged which scroll down as new faults are received.
Flow-Rate /Min
XXXXX*
System Level
XXXX