PUMP DATA LOG
Main Menu
Sub Menu
Units
Defaults
Range
PUMP DATA LOG
Hours Run 1
hours
display
0 - 65535
*Hours Run 2
hours
display
0 - 65535
*Hours Run 3
hours
display
0 - 65535
*Hours Run 4
hours
display
0 - 65535
*Hours Run 5
hours
display
0 - 65535
*Hours Run 6
hours
display
0 - 65535
Pump Starts 1
number
display
0 - 65535
*Pump Starts 2
number
display
0 - 65535
*Pump Starts 3
number
display
0 - 65535
*Pump Starts 4
number
display
0 - 65535
*Pump Starts 5
number
display
0 - 65535
*Pump Starts 6
number
display
0 - 65535
Pump Starts Last Hr
number
display
0 - 65535
Analogue Input 1
%
display
0.00 - 100.00
Analogue Output 1
%
display
0.00 - 100.00
Digital Input State
1 - 12
display
X for Active
Digital Output State
1 -4
display
X for Active
Curr & max retry
number
display
0 – 50 0 – 50
Temperature
degrees C display
0 - 999
* Hours Run 2-6 are only visible if "Number of pumps" is set accordingly
* Pump Start 2-6 are only visible if "Number of pumps" is set accordingly
Hours Run Pump 1-6
Each pump has an hour run meter attached to record the
actual run time for each pump. The hour log will
accumulate all of the operation time for each pump in both
AUTOMATIC and MANUAL modes.
To reset the time press ENTER then DOWN and then ENTER again.
Pump 1-6 Starts
The SWO registers the number of starts that
each pump accumulates to assist in the tuning of the
system. This number can assist in the selection of the Cut In and Cut Out levels and the
run time settings. The starts do not increment when selected in MANUAL as this is
considered to be an override function.
To reset press ENTER then DOWN and then ENTER again.
Starts Last Hour
This registers the numbers of starts that the
TOTAL
SYSTEM
had over the past hour. This is the accumulation
of all of the Starts for all of the pumps and is designed to
assist in trouble shooting. The new number is accumulated
over a 10-min period and is updated at 10-minute intervals. To get a true hourly reading
the system must have been running for at least 1 hour. After the first hour the last 6
previous 10-minute readings are added together to get the Starts last hour reading.
To reset press ENTER then DOWN and then ENTER again.
Hours Run Pump1
XXXXX
Pump Starts 1
XXXXX
Starts Last Hour
XXXXX