Pump Control Panel
The interface for SWO Control Panel allows access for the operator to edit
values throughout the
menus.
Each pump is controlled by an individual Auto / Off / Manual Switch.
To enable a pump for operation
Press the ON/OFF/Manual Mode switch and the associated mode indicator will light up.
The selected pump is now available for operation in Automatic mode.
To disable a pump in Automatic Mode
Press the Mode switch until the Mode indicator light turns off.
To operate a pump on Manual
In order to operate a pump in manual mode, press and hold the mode select switch for
the relevant pump, after 3 seconds the system will start this pump in manual mode. The
mode indicator led will now start flashing at 2 times per second and the RUN indicator will
be on. To turn a manual pump off, press and release the switch when the RUN led turns
off. The pump is now disabled and to return it to Automatic press the Mode switch again
and the Mode indicator should turn on.
In order for this mode to be selected the Access Code must be entered.
MANUAL MODE PROTECTION
Pump protection settings apply to all pumps including those in manual mode.
NB: By default all pumps will be off when system is powered.
To edit menu data
Press the ENTER key to edit data in the required menu, the top line will flash if the
current menu is an editable screen. Use the UP and DOWN buttons to change the
selection, then press ENTER again to confirm the change.
1
2
1
1
9
8
7
6
5
4
3
Swor dfish+
M ult i Pump
Fixed Speed
Cont r ol Syst em
2
1
Input Indicators
Techsys
Cor por at ion
Access to Qualified Personnel Only
Pump ON/OFF/Manual
Switch (Mode)
(One for each pump)
Pump RUN Indicator
(One for each pump)
Input Activation
Indicators
Two line LCD
Display
ON/OFF Indicator
(One for each pump)