TIMING
TIMING
*Lo Level Delay
seconds
120
*OFF, 0 - 250
*High Level Delay
seconds
4
*OFF, 0 - 250
In Delay Timer
seconds
4
0 - 999
Out Delay Timer
seconds
1
0 - 999
Restart Delay
seconds
0
0 - 999
No Flow Timer
seconds
0
0 - 250
Input Delay Timer
seconds
120
0 - 999
*Press Trip Low Delay seconds
0
0 - 999
*Press Trip High Delay seconds
0
0 - 999
*Min Pump Runtime
seconds
60
0 - 240
*Max Pump Starts
per Hour 60
0 - 240
Low Level Shutdown Delay
Set this time to delay a Low Level Shutdown. It must
time out before the system will shut down in Low Level
mode. The range for this is “0-250 sec”.
If the Low level shutdown needs to be turned OFF it can be done by accessing the “Low
Limit Action” sub menu in the Configuration menu. If Low Limit Action is set to OFF the
Low Limit and the Low level Delay screens will then display ------OFF---- and can not be
altered. If OFF is selected then the system will ignore any low-level shutdown commands.
Be sure that you fully understand the repercussions of this setting as the Shutdown
settings are designed to protect both the pump and the system from damage.
The Low & High level delay timers are independent of each other and can be set to suit
individual needs.
High Level Shutdown Delay
Set this time to delay the High Level Shutdown. It must
time out before the system will shut down in High Level
mode. The range for this is “0-250 sec”.
If the High level shutdown needs to be turned OFF it can be done by accessing the “High
Limit Action” sub menu in the Configuration menu. If High Limit Action is set to OFF the
High Limit and the High level Delay screens will then display ------OFF---- and can not be
altered. If OFF is selected then the system will ignore any high-level shutdown
commands. Be sure that you fully understand the repercussions of this setting as the
Shutdown settings are designed to protect both the pump and the system from damage.
In Delay Timer
The IN DELAY TIMER is used to delay the starting of
additional pumps. When the system level increases
above the Cut In Level the system starts the first pump
according to the “restart” timer. Any additional pumps required will be started if the level
remains above the Cut In Level in single level mode (Multiple Level Mode will Display Cut
In Level 1 /2 etc for individual pump start levels) after the In Delay Timer has timed out.
The In delay timer is used to start every pump apart from the first pump after a restart.
This timer is designed to assist in the reduction of Short Cycling and allowing the system
to stabilise before additional pumps are started.
HiLevel Delay
XXX seconds
LoLevel Delay
XXX seconds
In Delay Timer
XXX seconds