16
all programs +2:
Sensor
T6
is not employed as room sensor, but as reference sensor for
feeding buffer tank (tank bottom).
Note: T6
must be set as standard sensor (
Std
) (see selector switch position
Mod
– Par
).
In position “
Par
” the use of sensor
T6
must be set:
rAS
T6
is used as room sensor
Std
T6
is no room sensor, frost protection at
T5
keeps active
Setting in menu mixer control parameter „
Mr
“:
Atr
= outdoor temperature control or
Fir
=
fixed value control
A5 = T1 > min1 & T1 > T6 + diff2
all programs +4:
Sensor
T5
is not employed as room sensor, but as reference sensor for
feeding buffer tank (tank bottom). Outdoor temperature control for heating circuit is not possi-
ble (not usable
with „all pr2).
Note
: Setting in menu mixer control parameter “
Mr
”:
Fir
= fixed value control, or using a room
sensor
rtr
=room temperature control.
A5 = T1 > min1 & T1 > T5 + diff2
all pr8:
Potential free contact
A5
is linked out with output
A2
.
all pr160:
Heating circuit pump is enabled only by buffer tank temperature
T2
and
not
by boiler temperature
T1
.
A1 = T2 > min2 & (heating = active)
similar programs to diagram above:
see program 85 and 86 (after diagram 80)
Time programs
are possible for heating circuit
A1
and hot water tank feeding
A2