25
Burner
requirement
Diagram 144:
Automatic boiler, tank, mixer for increasing return, heating circuit
pump, burner requirement
Sensors
Outputs
T1…. Automatic boiler
A1…. Feed pump
T2…. Tank center
A2…. Heating circuit pump
T3…. Tank bottom
A
3…. Mixer open
T4…. Return line boiler
A4…. Mixer close
T5…. Tank top
A5…. Burner requirement
T6…. Return heating circuit
Basic function (P144):
Controlling of buffer feed pump
A1
and heating circuit pump
A2
,
controlling of return temperature by mixer
A3&A4
, burner requirement
A5
(holding-circuit);
heating circuit control can be applied by pump speed control.
A1 = T1 > min1 & T1 > T3 + diff1
A2 = T5 > min2 & T5 > T6 + diff2 & T6 < max
A5 on = T2 < Vmin
A5 off = T3 > Vmax
Required settings:
min1
…switch-on thresh. T1
A1 min2
…switch-on thresh. T5
A2
max
…heating circuit return line T6
A2
diff1
…boiler T1 – tank T3
A1 diff2
… tank T5 – heating circuit T6
A2
V
min
…burner requirement
on
T2
A5 V
max
… burner requirement
off
T3
A5
mixer control parameter Mr (fixed value control Fir:T+20, T-20), time program,
optionally: pump speed control Pd2 for heating circuit pump A2
A1 off A2 off
T1 < min1 T5 < min2
diff1 diff2
A1 on
A2 on
T3 T6 > max
A2 off
Burner requirement
A5
ON
T2 < V
min
OFF
T3 > V
max