Installing the unit
CAUTION! ALWAYS PULL THE MAINS PLUG BEFORE OPENING THE CASE!
Unscrew the 4 screws at the edges of the case. The controlling electronic is situated in the
cover plate and is connected by a ribbon cable to the mains module, which is set in the basin
of the case. The basin of the case can be screwed on through the two holes to the wall using
the fastening screws provided (
with the cable bushings downwards
). For easier handling
the mains module can be token out of the case.
Electrical connection
Warning:
The electrical connection should only be made by a professional electrician in
accordance with the relevant local guidelines. The sensor lines may not be fed through the
same cable channel as the supply voltage.
Notice:
The system must be grounded to protect it from damage by lightening according to
regulations; sensor failure caused by electrical storms or electrostatic charging can usually
be traced to insufficient grounding.
All sensors and pumps resp. valves must be connected to the controller according to the
numbering of the chosen diagram. All sensor grounds are interconnected and fully inter-
changeable.
W..... root C
S...... make contact NO
Ö...... break contact NC
The relay output A4 can be made potential-free by setting the
jumpers
J1-J2-J3. For this
purpose the jumper J2 must be set in the center instead of jumpers J1 and J3 (standard).