Program 33:
Separated switch-on and switch-off thresholds for burner requirement
A5 on = T2 < min2 + diff2
A5 off = T2 > max
Program 34:
as program 33, but switch-off threshold on
T3
(holding-circuit).
A5 on = T2 < min2 + diff2
A5 off = T3 > max
Program 35:
Holding circuit with difference on nominal flow temperature
Vsoll
A1 = T2 > min2 & (heating = active)
A2 = T1 > min1 & T1 > T3 + diff1
A5 on = T2 < max or (T2 < Vsoll + diff1 & (heating = active))
A5 off = T2 > max & (T3 > Vsoll + diff2 & (heating = active))
Program 36:
Heating circuit pump and burner requirement are separated.
A1 = T2 > min2 & (heating = active)
A2 = T1 > min1 & T1 > T3 + diff1
A5 = T3 < max
all pr8:
Buffer feed pump A2 is switched on immediately with burner requirement
(for fuel value units with minimum circulation quantity of water)
A2 = A2 or A5
Time programs
are possible for heating circuit
A1
and burner requirement
A5
. For
A5
the
time program manages only on the hot water requirement
A2
, because the burner require-
ment is linked with
A1
(heating active).
A1 off
A2 off
T2 < min2 T1 < min1
diff1
A1 on
A2
on
Switch-off cond.
HPu
T3
A1 off
Boiler requirement
A5
OFF
T2 > max
and
heating active
&
T3 > Vsoll + diff2
(Vsoll = nominal flow temperature)
Boiler requirement
A5
ON
T2 < max
or
heating active
&
T2 < Vsoll + diff1