Program 85:
A5
is a feed pump between boiler and buffer tank
T2
;
A2
is the feed pump
between boiler and hot water tank
T3
.
A1 = T2 > min2 & (heating = active)
A2 = T1 > min1 & T1 > T3 + diff1 & T3 < max
A5 = T1 > min1 & (T1 > T2 + diff2)
Program 86:
A1
and
A2
as program 85, but
A5
refers to
T6
(no room sensor).
Note: T6
must be set as standard sensor (
Std
) (see selector switch position
Mod
– Par
).
A5 = T1 > min1 & (T1 > T6 + diff2)
Time programs
are possible for heating circuit
A1
, solar circuit
A2
and burner requirement
A5
.
A1 off
A2 off
A5 off
T2 < min2 T1 < min1 T1 < min1
diff1 diff2
A1 on
A2
on
A5 on
Switch-off cond.
HPu
T3 > max T2
A1 off
A2 off