45
Legionella protection function LES
For avoiding production of legionellae this protection function can be activated.
After lapse of cycle time (tc) tank temperature is heated up to nominal temperature (C) be-
ginning from start time (h) (depending to program).
tc
= cycle time for legionella protection
function
Setting range: 0 to 9 days
ew
= tc 0
h
= Start time of heating up phase
Setting range: 0 to 23 (11 pm)
ew
= h 17 (5 pm)
C
= Nominal heating up temperature of tank
Setting range: 0 to 99°C
ew
= C 70
Input loop starts again
Exit from menu happens by pressing the yellow „
Eingabe
“ key for 2 seconds, turning the
selector switch or automatically after one minute.
2 sec
2 sec
short
short
short
Setting of cycle time
Start time of heating up phase
Setting of heating up temperature