52
Technical Data
Power supply:
230V +-10%, 50- 60Hz,
Power input:
max. 4 VA
Fuse:
3.15 a fast acting (device & output)
Supply cable:
3x 1mm² H05VV-F conforming to EN 60730-1
Protection class:
IP40
Allowed ambient
temperature:
0 to 45°C
Sensors:
Pt1000, accuracy between 0 and 1000°C: +-0.35K
Tank sensor BFPT1000:
Diameter 6 mm, according to immersion sleeves, incl. 2 m cable
(up to 90°C continuous load)
AUSPT:
Outdoor sensor in mounting housing (light grey)
RASPT:
Room sensor with possibility of remote control and switching be-
tween operating modes
Difference temperature:
adjustable from 0 to 99°C (diff)
Thresholds:
adjustable from 0 to 150°C (min, max)
Hysteresis:
adjustable from 1 to 9°C per 64°C
Speed control:
30 speed stages result in change of amount of max. 1:10 .
Regelung auf Absolutwert , Differenz und Absolutwert nach Ereignis
Temperature display:
from -50 to +199°C
Resolution:
from -9.9 to 100°C with 0.1°C, otherwise 1°C
Accuracy:
typ. 0.4 and max. +-1K in range 0 to 100°C
Outputs:
Triac output 1 and output 2 (minimum load of 20W required)
Relay contacts outputs 3, 4 and 5
Rated current load A1, A2:
250V / 1.5 A,
Rated current load A3, A4, A5:
250V / 2.5A
Quantity delivered:
Controller with 6 temperature sensors (3 x BFPT1000, 1 x KFPT1000, 1 x RASPT, 1 x
AUSPT1000), 3 immersion sleeves 140mm, mounting material, mains cable with plug
Summary of Contents for HZR 65
Page 1: ...HZR 65 Version P5 6 7 EN Universal heating controller Operation Installation instructions en ...
Page 2: ......
Page 31: ...31 Schematic representation of setting values ...
Page 57: ......
Page 58: ......
Page 59: ......