24
Program 129:
As Program 128, but switch-off threshold of burner requirement refers to
T2
(holding-circuit).
A5 on = T1 < min2
A5 off = T2 < min2 + diff2
Program 130:
A5
has feed pump function instead of burner requirement. Sensor
T6
is not
employed as room sensor, but as tank sensor.
Note: T6
must be set as standard sensor (
Std
) (see selector switch position
Mod
– Par
).
In position “
Par
” the use of sensor
T6
must be set:
rAS
T6
is used as room sensor
Std
T6
is no room sensor, frost protection at
T5
keeps active
Setting in menu mixer control parameter „
Mr
“:
Atr
= outdoor temperature control or
Fir
=
fixed value control
A1 = T2 > min2 & (heating = active) or A2
A2 = T2 > min2 & T2 > T3 + diff1 & T3 < max
A5 = T1 > min1 & T6 + diff2
Program 131:
As program 130. Exchange of
A2
with
A5
.
A2 <=> A5
A1 off A2 off A5 off
T2 < min2 T2 < min2 T1 < min1
diff1 diff2
A1 on
A2 + A1 on
A5 on
Switch-off cond. HPu T3 > max T6
A1 off
A2 off