Diagram 16:
Automatic boiler, hot water tank, heating circuit, burner requirement
Sensors
Outputs
T1…. Boiler
A1…. Heat circuit pump
T2…. Tank top
A2…. Tank feed pump
T3…. Tank bottom
A3…. Mixer open
T4…. Heat circuit flow
A4…. Mixer close
T5…. Outdoor temperature
A5…. Burner requirement
T6…. Room sensor
Basic function (P16):
No buffer tank; tank feed pump =
A2
; burner requirement =
A5
.
For
sliding boiler operation without mixer
: It makes sense to set the thresholds min1 and
min2 to 5°C (=no function) and to activate the pump switch-off condition Vsoll < Vmin (Menu
HPu).
Heating not active: Switch-off the burner requirement when nominal tank temperature
max
is
reached. Tank feed pump is still active until boiler temperature falls below
min1
for discharge
of the boiler residual energy.
Required settings:
min1
…switch-on thresh. T1
A1,2 min2
…switch-on thresh. T1
A5
max
…limit tank T2
A2,5 diff1
…boiler T1 – tank T2
A2
diff2
…boiler T1 – Vsoll
A5
V
max
, V
min,
T+20, T-20, T
norm
, T
abs,
mixer control parameter Mr
heating pump parameter HPu, time program tp
A1 off
A2 off
T1 < min1 T1 < min1
diff1
A1 on
A2
on
Switch-off cond. T2 > max
HPu
(if heating = active)
A1 off
A2 off
Boiler requirement
A5
T2 < max
and
time program (A2)
or
heating active
and
T1 < min2
or
heating active
and
T1 < Vsoll + diff2
(Vsoll = nominal flow temperature)
A5 = burner
requirement
Pellets-
or fossil
fuel
boiler