Program 82:
Instead of burner requirement (program 80)
A5
is a hot water tank feed
pump. Sensor
T6
is no room sensor, but a tank sensor.
Note: T6
must be set as standard
sensor (
Std
) (see selector switch position
Mod
– Par
). In position “
Par
” the use of sensor
T6
must be set:
rAS
T6
is used as room sensor
Std
T6
is no room sensor, frost protection at
T5
keeps active
Setting in menu mixer control parameter „
Mr
“:
Atr
= outdoor temperature control or
Fir
=
fixed value control
A5 = T2 > min1 & T2 > T6 + diff2 & T6 < min2
Program 83:
A5
is a hot water tank feed pump. Therefore the sensor
T6
is situated in the
boiler.
Note: T6
must be set as standard sensor (
Std
) (see selector switch position
Mod
–
Par
).
Heating circuit pump
A1
is enabled by buffer tank or boiler temperature.
A1 = T2 > min1 or T6 > min2 & (heating = active)
A5 = T6 > min2 & T6 > T3 + diff2
Program 84:
Enable of heating circuit pump
A1
without observance of any energy source
temperature.
A5
is a feed pump between
T2
and
T3
without maximum threshold.
A1 = (heating = active)
A2 = T1 > T3 + diff1 & T3 < max
A5 = T2 < min2 & (T2 > T3 + diff2)
A1 off
A5 off
T2 < min1 T1 T2 < min1
diff1 diff2
A1 on
A2
on
A5 on
Switch-off cond. HPu T3 > max T6 > min2
A1 off
A2 off A5 off