Commission and Test
Commission and Test
Commission and Test
Commission and Test of the Controller
of the Controller
of the Controller
of the Controller
Prior to using the SOLOgarde system, it is necessary to test and commission it.
Ensure that the jumper links are fitted as required. Apply power to the SOLOgarde controller.
Check that the green Activity light is flashing. It should indicate a double flash
every two seconds showing that the controller is running.
If the alarm is sounding (indicated by three successive bleeps of the SOLOgarde
sounder every 2 seconds and the red Activity light flashing), check that the door
is not open. The alarm will automatically silence after a period of 30 seconds.
Alternatively, use the hand-held programmer to reset the alarm (refer to section
3.4.6 of this manual for details on how to do this.)
If a hand-held programmer is available, connect this now. Refer to section 4.2 on
how to use the hand-held programmer. Also please read section 0, which
describes the Installation and Engineering features of the hand-held programmer.
Release the door by either pressing the Request to Exit button (if fitted) or by
briefly connecting the Egress
Egress
Egress
Egress terminal to the Common
Common
Common
Common terminal using a length of
wire. The following should occur:
You may hear an audible click from the relay
The LED marked relay is illuminated while the relay is operated (5 seconds)
The door is released