Modular UPS 25KVA~900KVA User Manual 71
Product Specification
7. Product Specification
This chapter provides the specifications of the product, including environmental
characteristics mechanical characteristics and electrical characteristics.
7.1 Applicable Standards
The UPS has been designed to conform to the following European and international
standards:
Table 7.1 Compliance with European and International Standards
Item
Normative reference
General safety requirements for UPS used
in operator access areas
EN50091-1-1/IEC62040-1-1/AS 62040-1-1
Electromagnetic compatibility (EMC)
requirements for UPS
EN50091-2/IEC62040-2/AS 62040-2
(
C3
)
Method of specifying the performance and
test requirements of UPS
EN50091-3/IEC62040-3/AS 62040-3
(
VFI SS
111
)
Note
The above mentioned product standards incorporate relevant compliance clauses with generic IEC
and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity
(IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and 60950).
7.2 Environmental Characteristics
Table 7.2 Environmental Characteristics
Item
Unit
Requirements
150/25
180/30
250/25
300/30
500/25
600/30
Acoustic noise level
at 1 meter
dB
65dB @ 100% load, 62dB @ 45% load
≤
70dB
Altitude of Operation
m
≤
1000,load derated 1% per 100m from 1000m to 2000m
Relative Humidity
%
0-95,non condensing
Operating Temperature
℃
0-40(for UPS only),Battery life is halved for every 10°C
increase above 20°C
UPS Storage
Temperature
℃
-40-70
7.3 Mechanical Characteristic
Table 7.3 Mechanical Characteristics for Cabinet
Item
Unit 150/25
180/30
250/25
300/30
500/25
600/30
Mechanical Dimension
(W*D*H)
mm 600*1100*2000 600*1100*2000
2000*1100*2000
Weight kg 170
220
620
Color N/A
Black
Protection Level
,
IEC60529
)
N/A IP20