FUNCTION SETUP GUIDE 
BRG850/1000/1350/1500AVRLCD 

K01-0000352-00

 

 

 

 

 

 

 

 

 

 

 

 

 

Power On:

 Press the POWER button for approximately 2 seconds and you will hear a short   

steady tone (1 second). Release the button after a short beep.   
 

Power Off:

 Press the POWER button for approximately 2 seconds and you will hear a short   

steady tone (1 second). Release the button after 2 short beeps.   

     

(

DISPLAY Button

)

:   

(1) (        ): Short press the button to scroll down the function / option menu and view the 

information about the UPS. 
 

(2) LCD On/Off: The default setting is the off position. The LCD display will dim if the buttons 

are not touched in 60 seconds. In Line Mode, press the button for 2 seconds to keep the LCD 

display always on. The LCD display will illuminate (and beep once). Press the button again 

for 2 seconds to turn off the LCD display. The LCD display will be off (and beep twice).   

In battery mode, the LCD is always on regardless of the settings. 

      (MUTE Button): 

 

(1) (      )

:

 Short press the button to scroll up the function / option menu and view the information about the UPS.   

 

(2) Audible Alarm: Press the button for 2 seconds to enable the audible alarm (beeps once) or disable (beeps twice) the audible alarm. 

The MUTE icon will appear on the LCD display when the audible alarm is disabled.   

Note: The default setting for the alarm is the on position.

 

ENTER (SETUP Button):

   

Setup Mode: Press the button for 2 seconds to access the setup mode’s 9 functions: Utility Power, MAX O/P Voltage, MIN O/P Voltage, 

Sensitivity, Low Battery Warning, Self Test, Event Reset, Return to Default Settings, and Return to Status Display.   

Short press the button (        ) or (        ) to view the functions. When a function is selected, short press the ENTER button to access the 

function’s options.   

Short press the button (        ) or (        ) to view the options. When the desired option is selected, short press the ENTER button to 

confirm the setting.   

Note: If there is no action for 8 seconds during setup, the LCD will leave setup mode and go back to the status display. The setting will 

not be confirmed. 

D SETUP Button:   

Pressing both buttons at the same time for 2 seconds will clear the EVENT counter (and beep twice).   

You can also clear the EVENT counter in setup mode. 
 

Refer to the following table for a detailed list of functions and their description. 

 

 

Function 

LCD Display 

Options 

Default 

Description 

Utility Power   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(CUS)* 

* Custom Setting: Only 

when MIN or MAX O/P 

Voltage is configured. 

Poor (97V~135V) 

 

 

Normal (100V~132V) 

 

 

Good (103V~129V) 

 

 

Escape to   

Function 

Menu 

Normal 

This function determines how the 

UPS will switch to AVR or Battery 

Mode. 

3 different output voltage ranges 

can be chosen according to the 

quality of the AC utility service in 

your location. 

If your utility service is not stable, 

you can select Poor (97V~135V). 

The UPS will go to AVR or Battery 

Mode less often to tolerate the 

utility power fluctuations. 

If your utility service is stable, you 

can select Good (103V~129V). The 

unit will go to AVR or Battery Mode 

more often. 

MAX O/P Voltage 

 

 

 

 

 

 

 

 

= fine tune the 

MAX O/P voltage 

H129~H135 

 

Escape to   

Function 

Menu         

H132 

In Utility Power settings, only 3 

types of fixed voltage ranges can 

be selected. However, you can fine 

tune the MAX O/P voltage with this 

option.       

If the utility voltage is usually high 

and the connected equipment can 

work in this condition, you can set 

the output voltage range higher to 

reduce how often the UPS goes to 

AVR Mode or Battery Mode. 

MIN O/P Voltage 

 

 

 

 

 

 

 

 

*

= fine tune the MIN 

O/P voltage 

L97~L103 

 

Escape to   

Function 

Menu         

L100 

In Utility Power settings, only 3 

types of voltage ranges can be 

selected. However, you can fine 

tune the MIN O/P voltage with this 

option.       

If the utility voltage is usually low 

and the connected equipment can 

work in this condition, you can set 

the output voltage range lower to 

reduce how often the UPS goes to 

AVR Mode or Battery Mode. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 