Product Specification
72 Modular UPS 25KVA~900KVA User Manual
Table 7.4 Mechanical
Characteristics for Power Module
Item
Unit
25KVA
30KVA
Mechanical Dimension
,
W*D*H
mm 460*790*134 460*790*134
Weight kg
32
34
7.4 Electrical Characteristics
7.4.1 Electrical Characteristics (Input Rectifier)
Table 7.5 Rectifier AC input Mains
Item
Unit
Parameter
Grid System
\
3 N Ground
Rated AC Input Voltage
Vac
380/400/415(three-phase and sharing neutral with
the bypass input)
Rated Frequency
Vac
50/60Hz
Input voltage range
Vac
304~478Vac (Line-Line),full load
228V~304Vac (Line-Line),load decrease linearly
according to the min phase voltage
Input Frequency range
Hz
40~70
Input Power factor
PF
>0.99
THDI THDI
%
<3% (full Linear Load)