Modular UPS 25KVA~900KVA User Manual 9
Product Introduction
2.3.6 Auto-restart Mode
The battery may become exhausted following an extended AC mains failure. The
inverter shuts down when the battery reaches the End of Discharge Voltage (EOD).
The UPS may be programmed to “System Auto Start Mode after EOD”. The system
starts after a delay time when the AC mains recovers. The mode and the delay time
are programmed by the commissioning engineer.
2.3.7 Frequency Converter Mode
By setting the UPS to Frequency Converter mode, the UPS could present a stable
output of fixed frequency (50 or 60Hz), and the bypass static switch is not available.
2.4 UPS Structure
2.4.1 UPS Configuration
The UPS configuration is provided in Table 2.1
Table2.1 UPS Configuration
Item
Components
Quantity/
pcs
Remark
6-slot Cabinet
Manual Bypass
1
Requisite, factory installed
Bypass & Monitoring
module
1
Requisite, factory installed
Dust filter
1
Optional.
10-slot Cabinet
Manual Bypass
Requisite, factory installed
Bypass & Monitoring
module
1
Requisite, factory installed
Dust filter
1
Optional.
20-slot Cabinet
Power distribution cabinet
(CB of Input, Bypass Input,
Output and Manual Bypass)
1
Requisite, factory installed
Monitoring unit
1
Requisite, factory installed
Bypass unit
1
Requisite, factory installed
Dust filter
1
Optional
30 KVA
Power module
Power module
1-20
Requisite, installed on site.
25 KVA
Power module
Power module
1-20
Requisite, installed on site.
2.4.2 UPS Outlook
The UPS outlook is shown as Fig.2-9 to Fig. 2-11.