Modular UPS 25KVA~900KVA User Manual 47
UPS and Module Control Panel
Submenus
MM-DD-YY
DD-MM-YY
YY-MM-DD
2014-02-14 11:28:42
Setting interface
Fig.4-10 Setting menu
The submenus are listed on the right side of the Setting page. Users can enter each of
the setting interfaces by touching the relevant icon. The submenus are described in
details below in Table 4.8.
Table 4.8 Description of each submenu of Setting
Submenu
Name
Contents
Meaning
Date&Time
Date format setting
Three formats: (a) year/month/day, (b)
month/date/year
,
(c) date/month/year
Time setting
Setting time
Language
Current language
Language in use
Language selection
Simplified Chinese and English selectable
(
The setting taking action immediately
after touching the language icon
)
COMM.
Device Address
Setting the communication address
RS232 Protocol Selection
SNT Protocol, ModBus Protocol, YD/T
Protocol and Dwin
(
For factory use
)
Baudrate
Setting the baudrate of SNT, ModBus and
YD/T
Modbus Mode
Setting mode for Modbus:ASCII and RTU
selectable
Modbus parity
Setting the parity for Modbus
USER
Output voltage Adjustment
Setting the Output Voltage
Bypass Voltage Up Limited
Up limited working Voltage for Bypass
,
se10%
,
+15%
,
+20%
,
+25%
Bypass Voltage Down
Limited
Down limited working Voltage for Bypass
,
settable:-10%
,
-15%
,
-20%
,
-30%
,
-40%
Bypass Frequency Limited
Permitted working Frequency for Bypass
Settable
:
+-1Hz
,
+-3Hz
,
+-5Hz
Dust Filter Maintenance
Period
Setting Dust Filter Maintenance Period
Battery Number
Setting the number of the battery
(
12V
)