background image

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[email protected] / www.tuncmatik.com

 

 

 

NEWTECH PRO II X9 

1-2-3 KVA ONLINE   

UNINTERRUPTIBLE POWER SUPPLY 

USER MANUAL 

 

Summary of Contents for NEWTECH PRO II X9

Page 1: ...info tuncmatik com www tuncmatik com NEWTECH PRO II X9 1 2 3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL ...

Page 2: ... this guide 4 2 Installation and setup 4 2 1 Unpack checking 4 2 2 Real panel view 5 2 3 LCD control panel 7 2 4 Setup the UPS 7 3 Operations 9 3 1 Button operation 9 3 2 LCD display 10 3 3 UPS setting 13 3 4 Operating Mode Description 15 3 5 Operational Status and Mode s 16 3 6 Alarm or Fault reference code 17 4 Troubleshooting 18 5 Storage and Maintenance 19 6 Specification 20 ...

Page 3: ...ease transport the UPS system only in the original package to protect against shock and impact 1 2 Preparation Condensation may occur if the UPS system is moved directly from cold to warm environment The UPS system must be absolutely dry before being installed Please allow at least two hours for the UPS system to acclimate the environment Do not install the UPS system near water or in moist enviro...

Page 4: ...vice and faults The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains building wiring outlet components inside the UPS system are still connected to the battery and electrically live and dangerous Before carrying out any kind of service and or maintenance d...

Page 5: ...1 6 Symbols used in this guide WARNING Risk of electric shock CAUTION Read this information to avoid equipment damage 2 Installation and setup NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Unpack checking Don t lean the UPS when moving it out from the packaging Check the appear...

Page 6: ...5 2 2 Real panel view 1kVA standart 1kVA Ex Batt 2kVA Standart ...

Page 7: ... input 2 Network Fax Modem Surge Protection option 3 Input circuit breaker 4 EPO option 5 USB communication port option 6 RS 232 communication port 7 SNMP intelligent slot option 8 Output receptacles 9 Battery Terminal 10 Output Terminal ...

Page 8: ...200 208 220 230 240VAC models The power cord is supplied in the UPS package Step 2 UPS output connection For socket type outputs simply connect devices to the outlets For terminal type input or outputs please follow below steps for the wiring configuration a Remove the small cover of the terminal block b Suggest using AWG14 or 2 1mm2 power cords for 3KVA 200 208 220 230 240VAC models c Upon comple...

Page 9: ... provide advanced communication and monitoring options NOTE USB port and RS 232 port can t work at the same time Step 4 Turn on the UPS Press the ON button on the front panel for two seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 5 Install software For optima...

Page 10: ...r is normal press and hold this button for 2 seconds Then UPS will enter to bypass mode This action will be ineffective when the input voltage is out of acceptable range Up key Press this button to display previous selection in UPS setting mode Select Mute Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and outp...

Page 11: ...e LCD display 1 Input information display area input voltage and frequency 2 Output information display area output voltage and frequency 3 Battery information display area battery status and capacity 4 Load information display area UPS load 5 Logo 1 4 2 5 3 ...

Page 12: ...11 Item Interface Description Content Displayed 01 Input voltage 02 Battery voltage 03 Output voltage 04 Load ...

Page 13: ...perature Environment Temperature Note UDC9101 only has Heatsink Temperature 06 Firmware Version UPS model 07 CODE Operational status and mode 08 Alarm Code Warming Message All alarm codes are present when abnormal behavior s occur s ...

Page 14: ...seconds and then goes into the setting interface page Note Figure at left corner is the page number of the setting pages Item Settings Content Displayed 01 Mode setting Press select button Select to change the setting ECO CF or NOR Press UP button to select the previous setting Press DOWN button to select the next setting 02 Output voltage setting Press select button to change the setting 100 110 ...

Page 15: ...revious setting Press DOWN button to select the next setting 05 Bypass voltage upper limit setting Press select button to change the setting The bypass voltage upper limit range is 230 264Vac Press UP button to select the previous setting Press DOWN button to select the next setting 06 Bypass voltage lower limit setting Press select button to change the setting The bypass voltage lower limit range...

Page 16: ...hin acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at online mode Inverter led light ECO mode Energy saving mode When the input voltage is within voltage regulation range UPS will bypass voltage to output for energy saving Bypass led light Battery mode When the input voltage is beyond the acceptable range or power failure and alarm is soun...

Page 17: ...erload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every 10 second Bypass led light 3 5 Operational Status and Mode s item Content Displayed 1 Initialized 2 Standby Mode 3 No Output 4 Bypass Mode 5 Utility Mode 6 Battery Mode 7 Battery Self diagnostics 8 Inverter is starting up 9 ECO Mode 10 EPO Mode 11 Maintenance Bypass Mode 12 Fault Mode ...

Page 18: ... lit 26 Battery over voltage Once per second Fault LED blinking 29 Output Short circuit Once per second Fault LED blinking 31 Bypass over current Once per second BPS LED blinking 32 Overload Once per second INV or BPS LED blinking 33 No battery Once per second Battery LED blinking 34 Battery under voltage Once per second Battery LED blinking 35 Battery low pre warning Once per second Battery LED b...

Page 19: ...connected well Alarm code is shown as 26 and battery led blinking Battery voltage is too high or the charger is fault Contact your dealer Alarm code is shown as 34 and battery led blinking Battery voltage is too low or the charger is fault Contact your dealer Alarm code is shown as 32 and INV or BYPASS led blinking UPS is overload Remove excess loads from UPS output Alarm code is shown as 29 and F...

Page 20: ...ervice life 3 5 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 1...

Page 21: ...e Bypass high voltage point For 200 208 220 230 240 VAC models 230 264 setting the high voltage point in LCD from 230Vac to 264Vac Default 264Vac For 100 110 115 120 127 VAC models 115 132 setting the high voltage point in LCD from 115Vac to 132Vac Default 132Vac Bypass low voltage point For 200 208 220 230 240 VAC models 170 220 setting the low voltage point in LCD from 170Vac to 220Vac Default 1...

Page 22: ...ransfer to bypass when the utility is normal 110 130 UPS shuts down after 1minute at battery mode or transfer to bypass when the utility is normal 130 UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal 35 Ambient Temp 40 105 110 UPS shuts down after 1 minutes at battery mode or transfer to bypass when the utility is normal 110 UPS shuts down after 3 sec...

Page 23: ...t kg 8 9 4 2 16 2 6 3 24 8 6 5 STANDARDS Safety IEC EN62040 1 IEC EN60950 1 EMC IEC EN62040 2 IEC61000 4 2 IEC61000 4 3 IEC61000 4 4 IEC61000 4 5 IEC61000 4 6 IEC61000 4 8 Derate to 80 of capacity when the output voltage is adjusted to 100 200 208VAC Product specifications are subject to change without further notice ...

Reviews: