Modular UPS 25KVA~900KVA User Manual 61
Operations
5.4 EPO
The EPO button located in the operator control and display panel (with cover to avoid
disoperation, see Fig.5-6) is designed to switch off the UPS in emergency conditions
(e.g., fire, flood, etc.).To achieve this, just press the
EPO
button, and the system will
turn off the rectifier, inverter and stop powering the load immediately (including the
inverter and bypass), and the battery stops charging or discharging.
If the input utility is present, the UPS control circuit will remain active; however, the
output will be turned off. To completely isolate the UPS, users need to open the
external mains input supply to the UPS. Users can restart the UPS by powering the
UPS again.
Warning
When the EPO is triggered, the load is not powered by the UPS. Be careful to use the EPO
function.
Fig .5-6 EPO Button
5.5 Installation of Parallel Operation System
For the 6-slot and 10-slot system ,it can have three UPS cabinets in parallel
,
which
can extend to a capacity of total 900KVA.Howerever, for the 20-slot system,
parallel is not supported at present.
Two UPS cabinets are connected as is shown in Fig.5-6.