Sun Confidential: Internal Only

Brian Jackson, July 2005

Sun Fire™ 3800 - 6800

Quick Reference Guide

Summary of Contents for Fire F3800

Page 1: ...Sun Microsystems Ltd Citygate Cross Street Sale Manchester M33 7JF UK Sun Confidential Internal Only Brian Jackson July 2005 Sun Fire 3800 6800 Quick Reference Guide...

Page 2: ...is a registered trademark in the U S and other countries exclusively licensed through X Open Company Ltd The OPEN LOOK and Sun Graphical User Interface was developed by Sun Microsystems Inc for its us...

Page 3: ...s pays Les produits portant les marques SPARC sont bas s sur une architecture d velopp e par Sun Microsystems Inc UNIX est une marques d pos e aux Etats Unis et dans d autres pays et licenci e exclusi...

Page 4: ...Sun Confidential Internal Only Please Recycle...

Page 5: ...Board ASICs 22 PCI I O Physical 23 cPCI I O Physical 24 I O Board Summary 24 Sun Fireplane Switch Boards 25 How it all bolts together 26 System Controller Boards 27 Nvram nvci SC flashproms 28 System...

Page 6: ...tp server for the System Controllers 56 setupplatform 57 Rebooting the system controller 58 Setting up the loghost 59 Edit syslog conf on the admin workstation 59 syslog Parsing Tools 59 Powering On a...

Page 7: ...used console busy 100 Navigating Between Shells 101 Escape sequence 102 showescape 102 setescape 102 Sun Fire Device Tree 103 Sun Fire Physical Device Mapping 105 Node Mapping 105 System Board Mapping...

Page 8: ...Sun Confidential Internal Only Sun Fire 3800 6800 Quick Reference Guide SunService Sun Microsystems Inc All Rights Reserved Enterprise Services...

Page 9: ...n and Service Manual 806 4211 xx Refer to the Platform Administration Manual and System Controller Commands Reference Manual specific to the firmware you are using For an exhaustive list of all Sun Fi...

Page 10: ...have been developed under the codename of serengeti They have gone through a number of name changes since their inception they are included below for your reference K6 Serengeti SP Serengeti 8 Sun Fir...

Page 11: ...Fire 3800 has the following features Support for 2 to 8 UltraSPARC III III Cu processors mounted on two system boards Up to 64 Gbytes of error checking and correction ECC memory Twelve hot swappable c...

Page 12: ...The Sun Fire 4800 has the following features Support for 2 to 12 UltraSPARC III III Cu processors mounted on three system boards Up to 96 Gbytes of ECC memory Sixteen PCI I O slots mounted on two I O...

Page 13: ...rucks ships and so on The Sun Fire 4810 has the following features Support for 2 to 12 UltraSPARC III III Cu processors mounted on three system boards Up to 96 Gbytes of ECC memory Sixteen PCI I O slo...

Page 14: ...tes of ECC memory Thirty two PCI I O slots or 16 hot swappable cPCI slots or combinations of PCI and cPCI mounted on four I O boards Support for up to four domains Three or four domains require two se...

Page 15: ...ects of the platform Refer to the Sun Fire Systems Site Planning Guide part number 805 7365 xx Dimensions clearance requirements weight Power requirements BTUs hr cooling requirements Power factor Con...

Page 16: ...d the L1 Sun Fireplane switch The system board L1 level 1 Sun Fireplane switching logic consists of an address repeater AR and 4 x data switch DX ASICs Each system board contains a system data control...

Page 17: ...f memory Each memory bank consists of four dual inline memory modules DIMMs which gives 8 x DIMMS per CPU See page 18 Memory capacity can also be mixed but not within the same bank The processor s L2...

Page 18: ...e any DIMMs installed in its corresponding DIMM bank but a populated DIMM bank must have a corresponding CPU processor installed in order for that memory to be utilised The system board supports the f...

Page 19: ...enabled pass 2048M DRAM N0 SB2 P1 B0 L2 enabled pass 2048M DRAM N0 SB2 P1 B1 L1 enabled pass 2048M DRAM N0 SB2 P1 B1 L3 enabled pass 2048M DRAM N0 SB2 P2 B0 L0 enabled pass 2048M DRAM N0 SB2 P2 B0 L2...

Page 20: ...1 1 3 J14500 1 0 2 J14501 CPU B 1 1 2 CPU P1 J14400 1 0 1 J14401 1 1 1 J14300 1 0 0 J14301 1 1 0 J13600 0 0 3 J13601 0 1 3 J13500 0 0 2 J13501 CPU A 0 1 2 CPU P0 J13400 0 0 1 J13401 0 1 1 J13300 0 0 0...

Page 21: ...ut is clearly marked on the cabinets However remember that in the F6800 the System boards are numbered non sequentially from left to right SB0 SB2 SB4 SB1 SB3 SB5 platform Number of System Boards Slot...

Page 22: ...ard PCI logic supporting three 33 MHz 64 bit 5VDC cards Each PCI I O board contains a system data controller SDC Again the SDC multiplexes the console bus connections and acts as the brains behind the...

Page 23: ...810 platforms support an 8 slot PCI board illustrated below and a 4 slot cPCI I O board Note There are 6 slots which run at 33MHz and 2 slots which run at 33 66 MHz balanced across two schizo ASICs Ba...

Page 24: ...cPCI I O Physical Below is an illustration of the 6 slot cPCI board is used in the F3800 The F3800 only supports a 6 slot cPCI board The 4 slot cPCI board is very similar to the layout below I O Boar...

Page 25: ...ey are alternatively known as level 2 L2 switches and repeaters although the preferred name is the Sun Fireplane switch In the F3800 the equivalent of two Sun Fireplane switch board is integrated into...

Page 26: ...e second level switches are incorporated in the centerplane Transactions originating from the first level switches on the system and I O boards are sent to the second level switches The second level s...

Page 27: ...onnects the system controller to the console bus which in turn is connected to the system boards I O boards and Sun Fireplane switch boards Each system board I O board and Sun Fireplane switch board c...

Page 28: ...application called the ScApp which is held in an 8 MB flashPROM on board This is the sgsgsc flash file in the flashupdate patch The SC maintains a centralized TOD hostids and MAC addresses and its ow...

Page 29: ...ou have both SCs present during the boot sequence of the SSC you will get a messages indicating that clock failover is enabled Jun 06 10 32 23 4800a sc0 Platform SC Clock failover enabled If one of th...

Page 30: ...as scname sc Improved diagnostics recovery Firmware compatibility New Commands setfailover showfailover Modified Commands password setupplatform setupdomain showboards showdomain showplatform showrese...

Page 31: ...t a lower up front cost and the remainder of the CPU memory board cost is not paid until the resources are used by ordering COD right to use RTU licenses New Commands addcodlicense deletecodlicense sh...

Page 32: ...f the parameter hang policy is set to reset using the setupdomain command the SC automatically initiates an XIR and re boots the hung domain Dynamic Domain hostID MAC Address assignment Useful for run...

Page 33: ...ct data between host and client and also uses authentication mechanisms to identify hosts and clients The SC supports five SSH connections along with the serial port connection New Commands setescape...

Page 34: ...C V2s by running showsc v4u 6800a sc0 SC showsc SC SSC0 Main System Controller V2 SC Failover disabled Clock failover enabled SC date Tue Aug 10 16 06 27 BST 2004 SC uptime 6 days 7 hours 41 minutes 2...

Page 35: ...on system uniboards which are indicative of potential processor attach issues Another term you may see used is CVTM Core Voltage Telemetry Monitor v4u 6800a sc0 SC showlogs Jan 01 03 10 46 roc2s3 Dom...

Page 36: ...owing commands refer to the Sun Fire 3800 6800 Troubleshooting Manual 805 7364 xx clearerrorbuffer clear the contents of the error buffer showerrorbuffer show the contents of the error buffer testinte...

Page 37: ...ce manual failover to the other SC y do not prompt for confirmation n do not execute command if confirmation is requested h display this help message sc1 4800a sc setfailover force SC SSC1 Spare Syste...

Page 38: ...the SC Starting with firmware 5 12 we poll the DX and DCDS ASICs for parity errors This requires a JTAG scan since these ASICs don t have console bus access If you press the reset button in the middle...

Page 39: ...s 8 KBytes of serial electrically erasable programmable read only memory SEEPROM installed into all FRUs This SEEPROM is split into two sections One is read only static and the other is read write dyn...

Page 40: ...Incorporates six media access controller MAC addresses for the F6800 and four MAC addresses for F3800 F4800 and F4810 platform and component power on hours The ID board is considered a single FRU If t...

Page 41: ...ower assemblies is defective platform Total Number of Fan Trays Minimum Number of Fan Trays F6800 Four fan trays two in the front FT1 and FT3 and in the rear FT0 and FT2 One fan tray front FT1 and two...

Page 42: ...will give the best availability The Sun Fire platforms offer hot swappable and redundant N 1 power supplies Power supplies are interchangeable among the F6800 and F4810 platforms The F4800 platform h...

Page 43: ...Fire 6800 The F6800 platform has two DC power grids Grid 0 and Grid 1 The DC power supply assignments are as follows Power Grid 0 consists of power supplies PS0 PS1 and PS2 Power Grid 1 consists of p...

Page 44: ...stem controllers There are three light emitting diodes LEDs The three LEDs are color coded green amber and amber Each LED is described below Name Color and Symbol On Off Activated green The board is a...

Page 45: ...on Do not connect the two RTS s within an RTU to the same supply This is less reliable than having one connection only Use separate AC sources There is normally one redundant transfer unit in a Sun Fi...

Page 46: ...have a different meaning on the RTS than on the rest of the FRUs as shown LED Position LED Color State Meaning Left Green On Off Flashing The source is present and is OK The source is not present or i...

Page 47: ...t settings for serial port A of the system controller board are set up automatically by default and are set to 9600 baud eight data bits no parity and one stop bit Cable layout is System Controller In...

Page 48: ...roller from the serial port of a workstation tip hardwire If you cannot use TTY Port B on the workstation s serial port you must edit the etc remote file dv dev term b br 9600 el C S Q U D ie oe D Cha...

Page 49: ...ssage is normal for the first time you ssh into an SC On the admin ws the file HOME ssh known_hosts is created with the following details admin ws cat known_hosts 6800b sc0 127 88 169 96 ssh rsa AAAAB...

Page 50: ...ns continue yes no no yes Connection to 6800b sc0 closed by remote host Connection to 6800b sc0 closed admin ws You will now need to remove the line in HOME ssh known_hosts pertaining to the original...

Page 51: ...h a serial connection This way you will capture all messages from the system controller tip 9600 dev term a connected Power on the platform and the SC should run its SCPOST boot the RTOS and start the...

Page 52: ...reserved Use is subject to license terms Sun Fire System Firmware RTOS version 38 ScApp version 5 16 0 SC POST diag level off The date is Monday February 23 2004 2 37 07 PM GMT Feb 23 14 37 08 6800b...

Page 53: ...a 10 100BASE Ethernet RIO interface ERI controller This ERI controller can be hooked up into the network to manage the platform and domains Like any Ethernet interface the system controller requires...

Page 54: ...NMP queries you must enable the SNMP agent and configure SNMP specific parameters Configuring the segment mode Sun Fire platforms support multiple segments partitions By default the systems are placed...

Page 55: ...ntax of the setdate command is setdate v t time zone mmddHHMM cc yy SS Setting the Date and Time for the Shell You can set the TOD from the platform shell by using the setdate command followed by the...

Page 56: ...that could be copied over to etc inet ntp conf and edited it provides a configuration template for a server that listens to an external hardware clock synchronizes the local clock and announces itsel...

Page 57: ...enable remote access to the system controller select ssh or telnet If you want to use the Sun Explorer Data Collector you must select ssh or telnet Note Sun Explorer Data Collector version 4 2 does n...

Page 58: ...SB0 SB1 SB2 SB3 SB4 SB5 IB6 IB7 IB8 IB9 COD PROC RTUs installed 0 PROC Headroom Quantity 0 to disable 4 MAX 0 PROC RTUs reserved for domain A 0 MAX 0 PROC RTUs reserved for domain B 0 MAX 0 PROC RTUs...

Page 59: ...orm local0 notice var log messages platform local1 notice var log messages domain A local2 notice var log messages domain B local3 notice var log messages domain C local4 notice var log messages domai...

Page 60: ...latform with the exception of the SCs which always have power through the auxiliary 48V bus 6800b sc0 SC poweron all 6800b sc0 SC poweroff all For specific HPUs 6800b sc0 SC poweroff FT0 6800b sc0 SC...

Page 61: ...rmware indeed you do not need the Fireplane switches powered on The path to the firmware is via the console bus and bootbus The following components have flash PROMs System controller boards System bo...

Page 62: ...SB0 FP0 Ver 09 20 2004 21 26 14 1 5 18 0 Build_14 N0 SB0 FP1 POST Yes 12 09 20 2004 21 22 14 1 5 18 0 N0 SB0 FP1 OBP Yes 12 09 20 2004 21 21 14 1 5 18 0 N0 SB0 FP1 Ver 09 20 2004 21 26 14 1 5 18 0 Bu...

Page 63: ...sh images f is optional URL is required URL the URL of the directory containing the flash images supported protocols FTP and HTTP ftp userid password hostname path http userid password hostname path c...

Page 64: ...d man page Edit etc passwd etc shadow To set up anonymous ftp add the following entry to the etc passwd file In this example export ftp was chosen to be the anonymous ftp area and the shell is the non...

Page 65: ...rectory export ftp Updating directory export ftp admin ws mkdir export ftp pubandcopythepatchintoit cd export ftp pub unzip 114524 02 zip Archive 114524 02 zip creating 114524 02 inflating 114524 02 S...

Page 66: ...ScApp will be upgraded automatically during the next boot Do you want to continue no yes Feb 16 14 36 10 6800b sc1 Platform SC Stopping all services on this SC No boards can be updated Rebooting the...

Page 67: ...Present Getting MAC address for SSC1 MAC address is 0 3 ba 7 37 7d Hostname 6800b sc1 Address 192 77 43 115 Netmask 255 255 255 0 Attached TCP IP interface to eri unit 0 Attaching interface lo0 done G...

Page 68: ...ving ftp v4m 5o uk sun com pub 114523 01 sgcpu flash Validating Done Current firmware version 5 12 7 New firmware version 5 16 0 Programming N0 SB0 PROM 0 Erasing Done Programming Done Verifying Done...

Page 69: ...flash are different Proceeding with update Erasing flashprom sectors at address 0x20000000 11 11 100 Programming 11 11 100 Connecting to v4m 5o uk sun com Transferring sgsc flash via FTP 6799606 Compa...

Page 70: ...n s Peer Reset Feb 16 14 54 13 6800b sc0 Platform SC Clock Source 75MHz Feb 16 14 54 41 6800b sc0 Platform SC Chassis is in single partition mode Feb 16 14 57 46 6800b sc0 Platform SC Main System Cont...

Page 71: ...o clear the SC problem by pressing the reset button See page 38 A full platform shutdown is required to carry out this procedure Note Since the system controller has failed there will be no access to...

Page 72: ...all the platform and domain configurations and passwords The system controller will be rebooted when the restore in complete The date will need to be set in the platform and each domain Do you want t...

Page 73: ...1 6800 SC Replace the system controller using anti static procedures at all times Once SSC0 is hot plugged it will power on automatically run through SCPOST load RTOS and ScApp System controller failo...

Page 74: ...effect immediately The old password is no longer accepted You can remove the password by pressing Return at the Enter new password and Enter new password again prompts To set the password you see the...

Page 75: ...sc0 SC setdefaults You are about to reset all configuration data to default values All domain configurations ACLs passwords data buffers network settings and SSH host keys will be lost The system con...

Page 76: ...le from service mode showcodlicense showcodusage showcomponent showdate showdomain showescape showenvironment showerrorbuffer showfailover showfru showkeyswitch showlogs showplatform showresetstate Ac...

Page 77: ...ch running its own Solaris Operating Environment The system controller provides a shell interface for each defined domain to perform administrative and servicing tasks This shell is called the domain...

Page 78: ...ment 0 RP2 RP3 constitute segment 1 For the F3800 F4800 and F4810 platforms RP0 constitutes segment 0 RP2 constitutes segment 1 All connections between the Fireplane switch boards of one segment and o...

Page 79: ...wo domains A C F4800 One segment one domain A One segment two domains A B Two segments two domains A C F4810 One segment one domain A One segment two domains A B Two segments two domains A C F6800 One...

Page 80: ...r and are isolated on the Sun Fireplane interconnect When two domains share a segment they each get half the address bandwidth of a full system bus When only one domain is in a segment it uses the ful...

Page 81: ...0 SB1 On CPU Board Assigned Not tested A N0 SB2 On CPU Board Assigned Not tested A N0 SB3 On CPU Board Assigned Not tested A N0 IB6 On PCI I O Board Assigned Not tested A N0 IB7 On PCI I O Board Assig...

Page 82: ...IB6 On PCI I O Board Assigned Not tested A N0 IB7 On PCI I O Board Assigned Not tested C N0 IB8 On PCI I O Board Assigned Not tested A N0 IB9 On PCI I O Board Assigned Not tested C 6800b sc0 SC Cauti...

Page 83: ...ror level max interleave scope within board interleave mode optimal reboot on error true hang policy notify reset OBP use nvramrc OBP default true OBP auto boot OBP default true OBP error reset recove...

Page 84: ...leave mode optimal reboot on error true hang policy reset OBP use nvramrc true OBP auto boot true OBP error reset recovery sync MAC Address HostID Domain C 08 00 20 d8 ab 62 80d8ab62 Loghosts Loghost...

Page 85: ...rmission to add or delete boards Configuring ACLs The ACLs for each domain can be set up using the setupplatform shell command Prefixing a slot name with a r removes the board from the list Prefixing...

Page 86: ...ormation There are three system controller commands used to administer the system controller s configuration data They are dumpconfig restoreconfig setdefaults Note It is NOT SUPPORTED to move the TOD...

Page 87: ...data URL the directory to store the data files supported protocol FTP ftp userid password hostname path h display this help message 6800b sc0 SC restoreconfig Command 6800b sc0 SC help restoreconfig...

Page 88: ...dumps sc0 4800a nvci Created ftp root root 172 16 40 5 SunFire dumps sc0 4800a tod sc0 4800a SC restoreconfig f ftp beej abc123 172 16 40 5 SunFire dumps This will restore all the platform and domain...

Page 89: ...power mode which allows you to remove the boards from the system The domain is not initialized at system power up on Powers on and initializes the domain The system controller brings the domain into...

Page 90: ...00 N0 SB4 P0 Copyright 2001 2004 Sun Microsystems Inc All rights reserved N0 SB4 P0 Use is subject to license terms N0 SB4 P0 Subtest Setting Fireplane Config Registers for aid 0x10 N0 SB4 P0 Subtest...

Page 91: ...N0 SB4 P0 Subtest I Cache Branch Predict Array Test N0 SB4 P1 Subtest I Cache Branch Predict Array Test N0 SB4 P0 Subtest I Cache Initialization N0 SB4 P1 Subtest I Cache Initialization N0 SB4 P0 Sub...

Page 92: ...N0 SB4 P1 Subtest 4M DTLB TAG Test N0 SB4 P0 Subtest 8K DTLB TAG Test N0 SB4 P1 Subtest 8K DTLB TAG Test N0 SB4 P0 Subtest 4M ITLB RAM Test N0 SB4 P1 Subtest 4M ITLB RAM Test N0 SB4 P0 Subtest 8K ITL...

Page 93: ...g Memory Registers Tests N0 SB4 P0 Subtest Disable Memory Controllers N0 SB4 P1 Subtest Disable Memory Controllers N0 SB4 P0 Subtest Mem Addr Control Reg Test N0 SB4 P1 Subtest Mem Addr Control Reg Te...

Page 94: ...4 P1 Subtest D Cache Functional N0 SB4 P0 Subtest D Cache Parity Functional N0 SB4 P1 Subtest D Cache Parity Functional N0 SB4 P0 Subtest D Cache Parity Tag Test N0 SB4 P1 Subtest D Cache Parity Tag T...

Page 95: ...SB4 P1 Subtest MTAG ECC errors test N0 SB4 P0 Subtest SYSTEM ECC errors test N0 SB4 P1 Subtest SYSTEM ECC errors test N0 SB4 P0 Subtest Ecache Tag ECC errors test N0 SB4 P1 Subtest Ecache Tag ECC err...

Page 96: ...oopback Tests for aid 0x1d N0 SB4 P0 Subtest PCI IO Controller block DMA loopback Tests for aid 0x1d N0 SB4 P0 Subtest PCI IO Controller Interrupt Tests for aid 0x1d N0 SB4 P0 Subtest PCI IO Controlle...

Page 97: ...eeded N0 SB4 P1 DCB_ENTER_OBP command succeeded Entering OBP Sun Fire 6800 OpenFirmware version 5 16 0 12 24 03 09 54 Copyright 2001 2004 Sun Microsystems Inc All rights reserved Use is subject to lic...

Page 98: ...t N0 SB4 P3 B0 L2 On blacklist N0 SB4 P3 B1 L3 On blacklist Board 8 Type PCI IO port 28 Status Pass Type PCI IO port 29 Status Pass Type PCI IO 10 ok probe scsi all ssm 0 0 pci 1d 700000 SUNW qlc 3 ss...

Page 99: ...ault reset uses an externally initiated reset xir to reset the processors in the domain showresetstate If error reset recovery none you have an opportunity to gather reset states using the domain shel...

Page 100: ...tion You can have a number of platform shells active but only one console connection Before doing the following make sure no one is using the console 6800b sc0 SC console a Connection refused console...

Page 101: ...e If you are connected to the system controller using a tip session use the command sequence to move from the Solaris Operating Environment or OpenBoot PROM to the system controller domain shell Refer...

Page 102: ...s a platform shell command 6800b sc0 SC showescape 6800b sc0 SC Change the escape sequence using the setescape command setescape 6800b sc0 SC help setescape setescape set system controller escape sequ...

Page 103: ...connected to the schizos as pci 1 pci 2 pci 3 This is misleading This will only be the case for certain cards e g qfe sunswift A PCI Single FC Host Adapter in slot 0 for example will be qlc 1 Refer t...

Page 104: ...scsi 3 disk block ssm 0 0 pci 18 700000 SUNW hme 2 1 network ssm 0 0 pci 18 700000 pci108e 1000 2 ssm 0 0 pci 18 700000 pci 1 pci ssm 0 0 pci 18 700000 pci 1 SUNW isptwo 4 scsi ssm 0 0 pci 18 700000 p...

Page 105: ...x Refer to the tables on the next two pages for AIDs Node Mapping The node identifier for standalone Sun Fire domains is always 0 Node identifiers other than 0 will be used when wildcat comes online F...

Page 106: ...ackets I O Mapping When mapping an I O device tree entry to a physical component in the system there are up to six nodes in the device tree that must be considered Node ID 0 for standalone Sun Fire do...

Page 107: ...00 pci 1 SUNW hme 0 1 ssm 0 0 pci 19 600000 pci 1 SUNW qfe 2 1 ssm 0 0 pci 18 600000 SUNW qlc 1 fp 0 0 Schizo AIDs hex in brackets Schizo PCI Bus Offset Bus A offset 600000 Provides 66 33 MHz PCI bus...

Page 108: ...ed Enterprise Services Eight Slot PCI I O Assembly Slot Assignments Logical layout as above physical layout as below pci 1 Slot 0 pci 2 Slot 1 pci 3 Slot 2 pci 18 700000 Schizo 0 pci 18 600000 pci 19...

Page 109: ...erved Enterprise Services Six Slot cPCI I O Assembly Slot Assignments Logical layout as above physical layout as below pci 1 Slot 0 pci 1 Slot 1 pci 1 Slot 2 pci 18 600000 Schizo 0 pci 18 700000 pci 1...

Page 110: ...vice Sun Microsystems Inc All Rights Reserved Enterprise Services Four Slot cPCI I O Assembly Slot Assignments Logical layout as above physical layout as below pci 1 Slot 0 pci 1 Slot 1 pci 1 Slot 2 p...

Page 111: ...defaults at the domain ok prompt sc0 4800a A setdefaults Do you want to restore the default values now no yes Feb 23 07 24 55 sc0 4800a Domain A SC Setting defaults for domain A sc0 4800a A 6800b sc0...

Page 112: ...false auto boot timeout 512 512 scsi initiator id 7 7 powerfail time 0 0 fcode debug true true output device sgc sgcn input device sgc sgcn load base 0x4000 0x4000 boot command boot boot auto boot tr...

Page 113: ...in in effect even after a power cycle Caution Adjust configuration variables with caution These NVCI variables determine the startup routine of the system so their configuration if incorrect can cause...

Page 114: ...8 700000 pci 1 SUNW isptwo 4 sd 0 0 disk1 ssm 0 0 pci 18 700000 pci 1 SUNW isptwo 4 sd 1 0 disk2 ssm 0 0 pci 18 700000 pci 1 SUNW isptwo 4 sd 2 0 disk3 ssm 0 0 pci 18 700000 pci 1 SUNW isptwo 4 sd 3 0...

Page 115: ...sk ssm 0 0 pci 1a 700000 pci 1 SUNW isptwo 4 sd 0 0 xnet ssm 0 0 pci 1a 700000 pci 1 SUNW hme 0 1 diskc ssm 0 0 pci 1c 700000 pci 1 SUNW isptwo 4 sd 0 0 netc ssm 0 0 pci 1c 700000 pci 1 SUNW hme cdrom...

Page 116: ...inID A ADInfo 1 SCAPP 15 0 Time Fri May 02 14 51 44 GMT 01 00 2003 FRU List Count 2 FRU PN 5014953 FRU SN 001494 FRU LOC RP0 FRU PN 5014362 FRU SN 015432 FRU LOC N0 SB0 Recommended Action Service acti...

Page 117: ...ed unusable unlicensed failed or disabled board N0 SB4 May 02 14 54 54 sc0 Domain A SC No usable Cpu board in domain setkeyswitch operation did not complete keyswitch is standby Note There is no manua...

Page 118: ...ory E cache 8 MB R freq 750 MHz A freq 750 MHz port 3 Status Pass Type CPU Memory E cache 8 MB R freq 750 MHz A freq 750 MHz Board 2 Type CPU Memory port 10 Status Pass Type CPU Memory E cache 8 MB R...

Page 119: ...Status RP0 Suspect N0 SB0 Suspect N0 SB2 Suspect N0 SB4 Suspect sc0 SC service service sc0 SC showerrbuffer ErrorData 0 Date Fri May 02 14 51 44 GMT 01 00 2003 Device partition0 domain0 SB0 ar0 ErrorI...

Page 120: ...rrorData 6 Date Fri May 02 14 52 16 GMT 01 00 2003 Device partition0 domain0 SB2 ar0 ErrorID 0x10421009 Register SafariPortError9 0x290 0x00000001 AdrPErr 00 00 0x1 Address parity error ErrorData 7 Da...

Page 121: ...rrors on their interconnect to RP0 this is my suspect FRU Re assigning HostID MAC Address I want to bring up my domain but I don t want to use RP0 I have software which is hostid licensed At 5 15 x an...

Page 122: ...ode Configure chassis for single or dual partition mode single dual sc0 SC deleteboard sb0 sb2 sb4 ib6 ib8 sc0 SC addboard d c sb0 sb2 sb4 ib6 ib8 sc0 SC showboard Slot Pwr Component Type State Status...

Page 123: ...ff ffffffff Domain C 08 00 20 d8 86 b3 80d886b3 Domain D ff ff ff ff ff ff ffffffff SSC0 08 00 20 d8 86 b7 80d886b7 SSC1 08 00 20 d8 86 b8 80d886b8 System Serial Number 105M2F39 Chassis HostID 80d886b...

Page 124: ...86b4 Domain C ff ff ff ff ff ff ffffffff Domain D ff ff ff ff ff ff ffffffff SSC0 08 00 20 d8 86 b7 80d886b7 SSC1 08 00 20 d8 86 b8 80d886b8 System Serial Number 105M2F39 sc0 SC Re setting component h...

Page 125: ...Auto diagnosis Engine ADE Case Study Sun Confidential Internal Only 125 SunService Sun Microsystems Inc All Rights Reserved Enterprise Services...

Page 126: ...Auto diagnosis Engine ADE Case Study Sun Confidential Internal Only 126 Sun Fire 3800 6800 Quick Reference Guide SunService Sun Microsystems Inc All Rights Reserved Enterprise Services...