Faults
Fault 1281: Steam Purge Actuator Is Disconnected
Indicates the CANBUS heartbeat communication is offline.
Causes
Troubleshooting
Fixes
• Steam purge actuator
disconnected.
• Connect steam purge actuator.
• Blown fuse #9 (main fuse
block).
• Check fuse for blown
symptoms.
• Replace fuse #9 (5 amp).
• Wrong CAN address on the
steam purge actuator.
• Change the address to 0, then re-address the actuator
(See Test 1008).
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
Fault 1282: Steam Purge Actuator Is Not Calibrated
Indicates the actuator has not been programmed by the factory.
Causes
Troubleshooting
Fixes
• Faulty actuator.
• Replace actuator.
Fault 1283: Steam Purge Actuator Stuck / Jammed
Indicates the internal encoder does not match the commanded actuator position.
Causes
Troubleshooting
Fixes
• Obstruction in valve.
• Remove obstruction.
• Faulty actuator.
• Replace actuator.
Fault 1284: Top Steam Actuator Is Disconnected
Indicates the CANBUS heartbeat communication is offline.
Causes
Troubleshooting
Fixes
• Top steam actuator
disconnected.
• Connect top steam actuator.
• Blown fuse #12 (main fuse
block).
• Check fuse for blown
symptoms.
• Replace fuse #12 (5 amp).
• Wrong CAN address on the top
steam actuator.
• Change the address to 0, then re-address the actuator
(See Test 1008).
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
Fault 1285: Top Steam Actuator Is Not Calibrated
Indicates the actuator has not been programmed by the factory.
Causes
Troubleshooting
Fixes
• Faulty actuator.
• Replace actuator.