© 2021 Staheli West
124
Faults
Fault 1060: Louver Open (Too Long) in Start
Fault 1061: Louver Not Open in Pre-Purge
Fault 1062: Louver Not Open in Purge
Fault 1063: Louver Closed (Too Long) in Start
Fault 1064: Louver Not Closed in Pre-Ignition
Fault 1065: Louver Not Closed in Spark Ignition
Fault 1066: Louver Not Closed in Main Ignition
Indicates the louver was not in the proper position.
Causes
Troubleshooting
Fixes
• Faulty louver actuator.
• Test in manual mode to see if
louver actuator moves.
• Swap louver actuator with
water purge actuator.
• Swap/Replace louver actuator.
• Obstructed path of the louver
actuator.
• Remove actuator and manually
move the louver to feel if there is
any resistance or obstructions.
• Remove obstructions.
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
Fault 1100: Burner Controller Watchdog Reset
If problem persists: contact dealer / replace controller
Fault 1101: Battery Voltage High (Over 16.5 V Burner Controller)
Check tractor battery. If problem persists: contact dealer / replace controller.
Fault 1102: Battery Voltage Low (Under 8.8v Burner Controller)
Check tractor battery. If problem persists: contact dealer / replace controller.
Fault 1103: Burner Controller Output Supply 1 Voltage Low
Check tractor battery. If problem persists: contact dealer / replace controller.
Causes
Troubleshooting
Fixes
• Blown fuse #27 (main fuse
block).
• Faulty spark coil causing blown
fuse #27.
• Check fuse for blown
symptoms.
• Inspect spark coil wiring and
connection.
• Replace fuse #27 (2 amp).
• Replace spark coil.
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.