Faults
Fault 1265: Boiler Water Level Too High (Over 8 Inches)
Indicates the boiler water level has been reading more than 8 inches for > 20 seconds.
Causes
Troubleshooting
Fixes
• Wet layup.
• Have you performed a wet
layup recently? Wet layup fills the
boiler completely full of water.
• Drain water from boiler to
desired level.
• Faulty feed water actuator.
• Test in manual mode.
• Replace feed water actuator.
• Poor water quality.
• See fault 2003.
• Drain boiler and refill with fresh
water.
• See fault 2003 for more causes
and fixes.
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
Fault 1266: Boiler Water Level Too High (Over 10 Inches)
Indicates the boiler water level has been reading more than 10 inches for > 20 seconds.
Causes
Troubleshooting
Fixes
• Wet layup.
• Have you performed a wet
layup recently? Wet layup fills the
boiler completely full of water.
• Drain water from boiler to
desired level.
• Faulty feed water actuator.
• Test in manual mode.
• Replace feed water actuator.
• Poor water quality.
• See fault 2003.
• Drain boiler and refill with fresh
water.
• See fault 2003 for more causes
and fixes.
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
Fault 1267: Fan Speed Over 4500 RPM
Causes
Troubleshooting
Fixes
• Faulty fan speed control valve.
• Disconnected fan speed control
valve.
• There are 2 speed control
valves. Open center and closed
center. Make sure the proper
setting is selected on the touch
screen.
• Replace fan speed control valve
open center.
• Replace fan speed control valve
closed center.
• Connect fan speed control
valve.
• Excessive flow from open center
tractor hydraulics.
• Reduce flow to <25 gpm.
• Buy a new tractor.