Faults
Fault 1269: Open Center Fan Speed Valve Short To Ground
Indicates the amperage draw is too high.
Causes
Troubleshooting
Fixes
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
• Faulty valve.
• Replace valve.
Fault 1270: Fan ON/OFF Solenoid Disconnected
Indicates an open circuit during use.
Causes
Troubleshooting
Fixes
• Fan ON/OFF solenoid
disconnected.
• Connect the Fan ON/OFF solenoid.
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
Fault 1271: Fan ON/OFF Solenoid Short To Ground
Indicates the amperage draw is too high.
Causes
Troubleshooting
Fixes
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
• Faulty valve.
• Replace valve.
Fault 1272: Feed Water Pump ON/OFF Solenoid Disconnected
Indicates an open circuit during use.
Causes
Troubleshooting
Fixes
• Feed water pump ON/OFF
solenoid disconnected.
• Connect the feed water pump ON/OFF solenoid.
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
Fault 1273: Feed Water Pump ON/OFF Solenoid Short To Ground
Indicates the amperage draw is too high.
Causes
Troubleshooting
Fixes
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
• Faulty valve.
• Replace valve.