Faults
Fault 1128: High Fire on/off Solenoid Short To Ground
Indicates the amperage draw is too high.
Causes
Troubleshooting
Fixes
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
• Faulty solenoid.
• Replace solenoid.
Fault 1129: Safety Fuel Solenoid Disconnected
Indicates an open circuit during use.
Causes
Troubleshooting
Fixes
• Solenoid disconnected.
• Connect solenoid.
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
• Faulty solenoid.
• Replace solenoid.
Fault 1130: Safety Fuel on/off Solenoid Short To Ground
Indicates the amperage draw is too high.
Causes
Troubleshooting
Fixes
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
• Faulty solenoid.
• Replace solenoid.
Fault 1131: Spark Coil Disconnected
Indicates an open circuit during use.
Causes
Troubleshooting
Fixes
• Solenoid disconnected.
• Connect solenoid.
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
• Faulty solenoid.
• Replace solenoid.
Fault 1132: Spark Coil Short To Ground
Indicates the amperage draw is too high.
Causes
Troubleshooting
Fixes
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
• Faulty solenoid.
• Replace solenoid.