Faults
Fault 1112: Burner Controller Output Supply 4 Voltage Low
Check tractor battery. If problem persists: contact dealer / replace controller.
Causes
Troubleshooting
Fixes
• Blown fuse #7 (main fuse
block).
• Faulty safety fuel solenoid
causing blown fuse #7.
• Check fuse for blown
symptoms.
• Inspect safety fuel solenoid
wiring and connection.
• Replace fuse #7 (2 amp).
• Replace safety fuel solenoid.
• Faulty wiring.
• Inspect the wiring for ground,
continuity, and proper voltage.
• Repair/Replace wiring.
Fault 1113: Burner Controller Output Supply 4 Voltage High
Check tractor battery. If problem persists: contact dealer / replace controller.
Fault 1114: Burner Controller Output Supply 4 Amperage High
Check tractor battery. If problem persists: contact dealer / replace controller.
Fault 1115: Flame Detector 12 V Supply Too Low
Triggers when voltage is under 10.8 V
Fault 1116: Flame Detector 12 V Supply Too High
Triggers when voltage is over 13.2 V
Fault 1117: Flame Detector Voltage Divider 8.5 V Too Low
Triggers when voltage is under 8.15 V
Fault 1118: Flame Detector Voltage Divider 8.5 V Too High
Triggers when voltage is over 8.85 V
Fault 1119: Burner Controller 5 V Supply Too Low
Triggers when voltage is under 4.5 V
Check tractor battery. If problem persists: contact dealer / replace controller.
Fault 1120: Burner Controller 5 V Supply Too High
Triggers when voltage is over 5.5 V
Check tractor battery. If problem persists: contact dealer / replace controller.