FJOG command, RJOG command (set value = 12, 13)
Forward and reverse jog frequency operation is enabled.
Set value = 12 FJOG command: Forward run by jog frequency reference (An-09)
at closed.
Set value = 13 RJOG command: Reverse run by jog frequency reference (An-09)
at closed.
Notes:
1. When FJOG command or RJOG command is input during running, FJOG command or RJOG command
has priority
2. When both FJOG and RJOG commands are closed for 500 ms or more, the inverter stops according to
the stopping method selection (Sn-04).
3. FJOG or RJOG command can be set individually.
○
12
External faults 5 to 8 (set values = 2X, 3X, 4x, 5X: X is 0 to F)
When external faults 5 to 8 are input, Ext. Fault 5 to 8 (EF5 to EF8) is displayed at
the digital operator, and the inverter operates according to combinations of four bits
shown in the table below. The hexadecimal equivalent of combinations of four bits
show below is set in the 1st digit of the setting value (2X, 3X, 4X, 5X) of external
faults 5 to 8.
Bit No.
0
1
0
External fault input:
NO - contact input
External fault input:
NC - contact input
1
External fault signal:
Always detected
External fault signal:
Detected during running only
3, 2
Selection of processing
at external fault detection
00: Ramp to a stop (major fault)
01: Coasting to a stop (major fault)
10: Ramp to a stop by bn-04 (major fault)
11: Operation to continue (minor fault)
<Example> External fault 5 is set to as follows :
NO-contact input (from terminal 5)
Signal is always detected
Processing is coasting to a stop