67
-
Function
Parameter
No.
Name
LCD Display
(English)
Description
Factory
Setting
Ref.
Page
Sn-23
Inverter ststion
address
Sn-23=01
Inverter Address
Inverter address can be set as 1~31
01
- -00
:
No parity
- -01
:
Even parity parity setting
- -10
:
Odd parity
- -11
:
not used
RS-485
commu-
nication
Function
Sn-24
RS-485
communication
protocol setting
Sn-24=0011
RS-485 protocol 00- -
:
2400 bps (bit/sec)
01- -
:
4800 bps baud
10- -
:
9600 bps rate
11- -
:
19200 bps setting
0011
101
Language Sn-25
LCD Language
displayed selection
Sn-25=0
Language select
0
:
English
1
:
Chinese
1 102
Sn-26
Multi-Function
Analog Output A01
Function Selection
Sn-26=00
Term. A01 Function
0
:
Ferquency command (10V/max
frequency command, Cn-02)
1
:
Output Frequency (10V/max Output
frequency)
2
:
Output Cueeent (10V/inverter rated
current)
3
:
Output Voltage (10V/input voltage,
Cn-01)
4
:
DC Voltage (10V/400VDC or 800VDC)
5
:
Output Power (10V/max. applicable
motor capacity)
0 102
Multi-
Function
Analog Output
Selection
Sn-27
Multi-Function
Analog Output A02
Function Selection
Sn-27=01
Term. A02 Function
0
:
Ferquency command (10V/max
frequency command, Cn-02)
1
:
Output Frequency (10V/max Output
frequency)
2
:
Output Cueeent (10V/inverter rated
current)
3
:
Output Voltage (10V/input voltage,
Cn-01)
4
:
DC Voltage (10V/400VDC or 800VDC)
5
:
Output Power (10V/max. applicable
motor capacity)
1 102
-
Sn-28 Not
used
Sn-28=0
Reserved
-
-
-
-
Sn-29 Not
used
Sn-29=0
Reserved
-
-
-
PA-PID Card
Function
Selection
Sn-30
Pump Operation
Mode Selection
Sn-30=0
Run-Mode Select
0
:
PA-PID Card ineffective
1
:
Fixed inverter driving mode, stop all the
pumps by first-run-last-stop sequence.
2
:
Fixed inverter driving mode, stop the
pump drived by the inverter only.
3
:
Fixed inverter driving mode, stop all the
pumps by first-run-first-stop sequence.
4
:
Cycled inverter driving mode, stop all the
pumps by first-run-first-stop sequence.
5
:
Cycled inverter driving mode, stop the
pump drived by the inverter only.
0 103