(37) Auto Restart Time Interval (Cn-62)
Set the auto reset / restart operation time interval when the number of auto reset /
restart operation is more then 2.
The setting range of Cn-62 is 0~20 sec, the auto restart time interval is minimum
baseblock time (Cn-40) when the setting value of Cn-62 is 0.
The auto restart time interval is the setting value of Cn-40 when the setting value
of Cn-62 < Cn-40.
The auto restart time interval is the setting value of Cn-62 when the setting value
of Cn-62 > Cn-40.
(38) Motor Overheat Protection Time (Cn-63)
Time delay for motor overheat protection when the detected temperature of PTC
thermistor motor temperature sensor reached the trip level.
Generally, it is not needed to change the set value of Cn-63, The factory setting is
150%, 1 minutes motor overheat capability. Refer to motor overheat protection
setting of Sn-19.