(2) Adjusting PID contant
Refer to page, the block diagram of PID control selection, using the following
procedure to activate PID control and then adjust it while monitoring the
response.
(
I
) Enable PID control function (Setting Sn-19 = 09, and if any constant
Sn-15 ~ 18 setting value is 66, then none of control terminal
○
5
~
○
8
can be closed).
(
II
) Increase the proportional gain P (Bn-14) as far as possible without
creating oscillation.
(
III
) Reduce in integral time I (Bn-15) as far as possible without creating
oscillation.
(
IV
) Increase the differential time D (Bn-16) as far as possible without
creating oscillation.
First set the individual PID control constants, and then make fine
adjustments.
Reducing Overshooting
If overshooting occurs, shorten the derivative time D (Bn-16) and lengthen
the integral time I (Bn-15)
Rapidly Stabilizing Control Status
To rapidly stabilize the control conditions even when overshooting occurs,
shorten the integral time I (Bn-15) and lengthen the derivative time D (Bn-16)
After adjustment
Time
Response
Before adjustment
After adjustment
Time
Response
Before adjustment